6. Troubleshooting
Press the “UP’ or “DOWN” key to check if there are any more failure codes.
The solutions to the problems can be found with their corresponding code.
Malfunction
Code
Reason
Solution
High pressure protection has
appeared 3 times in 30 mins
P1
High pressure protection is too
frequent
Check the below
solutions to failure
P1/P2/P3
High pressure protection
P2
Discharge pressure is too high
Condenser outlet temp. over
high
P3
Condenser coil temp. is too high
Evaporator outlet temp.
sensor failure
P5
This temp. sensor is broken or in
open/short circuit
Check or replace temp.
sensor
Evaporator inlet temp. sensor
failure
P6
This temp. sensor is broken or in
open/short circuit
Check or replace temp.
sensor
Condenser outlet temp. sensor
failure
P7
This temp. sensor is broken or in
open/short circuit
Check or replace temp.
sensor
Humidity sensor failure
P8
Humidity sensor is broken or in
open/short circuit
Check or replace
humidity sensor
Motor feedback signal failure
E0
The feedback wiring has a bad
connection or fan motor is damaged
Check the feedback
wiring of the fan motor
or replace the fan motor
Solution to failure P1/P2/P3:
1)
If P1/P2/P3 appears together with other failures, please solve the others first.
2)
If there is no other failures of P3~E0, and P1 & P2 still exist, please disconnect the power to the unit and
connect again after 1 hour.
3)
If only P3 exists, please keep the fan running for 30 mins. If P3 still exists after the running, please disconnect
the power to the unit and connect again after 1 hour.
Note: Please contact Technical Service if failures cannot be solved.