A. Form of Troubleshooting

Check whether there is fault on 

pressure switch or refrigerant loop

 

 

 

 

Check whether system compressor

is in normal operation

     

 

Protection/fault

Standby

 

Normal booting

Water inlet temp. sensor error 

Ambient temp. sensor error

Antifreezing protection

Water flow protection

Cause

Water inlet temp sensor is in open

 circuit or short circuit

Check and replace temp. sensor

Water outlet temp sensor is in

 open circuit or short circuit

Ambient temp sensor is in open 

circuit or short circuit

 

 

 

 

Check and replace temp. sensor

Check and replace temp. sensor

Way of troubleshooting

Abnormal communication between 
remote controller and mainboard 

Flow is inadequate

 

Check water flow , and whether 

water system is damaged

Ambient temperature is too low

Ambient temperature is too low

There is no or little water in water system

Check water flow , and whether 

water system is damaged

Fault

display

NO

NO

P01

P02

P04

P07

P08

High-pressure protection

Low-pressure protection

E01

E03

E02

Suction temp. sensor is in open

circuit or short circuit

 

 

 

 

Check and replace temp. sensor

Exhaust temp. Sensor is in open 

circuit or short circuit

Check and replace temp. sensor

High-pressure switch is disconnected

Low-pressure switch is disconnected

E07

E19

E29

Compressor load is too large

Suction pressure sensor is in open 
circuit or short circuit

Exhaust pressure sensor is in open

circuit or short circuit

 

 

 

 

Winter Level I antifreezing 

protection

PP2

Input voltage is too low, resulting in
too high input current

 

 

 

 

Input current is too high, exceeding 
effective value for protection current halt 

DC bus voltage

DC bus overvoltage

 halt  protection  value
DC bus voltage

DC bus overvoltage

 halt  protection  value

IPM current is too large

Temperature of IPM module is too high

Sensor is in short circuit or open circuit 

Temperature of power component is
 too high
Fault of current sampling

Compressor current is too high

Input voltage is in default phase

Default phase, step out or hardware 
damage on actuator

 

Fault of DSP and communication board

Fault of DSP and PFC

Fault of current sampling

Chip error

Inadequate magnetic force of compressor 

Check and replace exhaust pressure

sensor

 

Check and replace suction pressure 

sensor

Check and measure input voltage

Check and measure input current

Check and measure bus voltage

Check and measure bus voltage

Check and measure current as well
 as  adjust
Check and measure current as well
 as  adjust

Check and replace sensor

Reduce temperature and check
c

  omponent

Check and measure current as well 
as adjust
Check and measure voltage as well 
as adjust

Check and measure voltage and 

check  frequency  board  hardware

Check communication connection

Check communication connection

Check communication connection 

Check and measure current as well 
as adjust

P181

E21

E22

E24

E25

E27

E28

E29

E30

E32

E33

E35

E36

Water inlet temp.sensor error 

Suction temp. sensor error

Exhaust temp. sensor error

Suction pressure sensor error

Exhaust pressure sensor error

Winter Level II antifreezing 

protection

 

 

AC input undervoltage

protection

 

Exhaust over heat 

protection

AC input overcurrent 
protection halt

 

DC bus overvoltage
 protection

 

DC bus undervoltage
 protection

 

IPM overcurrent protection

 

IPM module overheat 
protection

 

Radiator temperature 
sensor error

 

Power component overheat 
protection halt 

 

IPM current sampling

 

Compressor overcurrent
 protection hault

 

Input voltage default phase

 

Failure of compressor 
booting

 

Fault of communication
 between DSP and PFC 

Fault of communication 
between  DSP and
 communication board 

Input voltage sampling

  

Fault of EEPROM

   

Compressor flux weakening 
protection alarm    

Fault of communication between 
actuator and Pc8002 

  

Check whether there is fault on 

pressure switch or refrigerant loop

Check whether chip is damaged and 
replace chip 

PP1

E37

 

E38

 

E39

 

E40

 

E41

 

EE8

 

Form of Troubleshooting

Form of Troubleshooting

B. Or make judgment and troubleshooting by reference to the following form

Failure 

Possible causes for the failure

Solutions 

Heat pump 

cannot

be started

1   Wrong power supply                 
2   power supply cable loose         
3   circuit breaker open 

1   shut off the power and check power supply;
2   check power cable and make right connection  
3   check for the cause and replace the fuse or 
     circuit breaker

Water pump is 

running with 

high noise or 

without water  

1   lack of water in the piping                     
2   much air in the water loop
3   water vavles closed              
4   dirt and block on the water filter    

1   check the water supply and charge water 
     to the piping; 
2   discharge the air in the water loop;
3   open the valves in water loop;
4   clean the water filter.

Heat pump 

capacity is low, 

compressor 

do not stop 

1   lack of refrigerant;                    
2   bad insulation on water pipe;  
3   low heat exchange rate on air side 
     exchanger;
4   lack of water flow 

1   check for the gas leakage and recharge the 
     refrigerant;  
2   make good insulation on water pipe;
3   clean the air side heat exchanger; 
4   clean the water filter

High compressor 

exhaust 

1   too much refrigerant                       
2   low heat exchange rate on air side 
     exchanger 

1   discharge the redundant gas                       
2   clean the air side heat exchanger 

Low pressure 

problem 

of the system

1   lack of gas                       
2   block on filter or capillary  
3   lack of water flow 
    

1   check the gas leakage and recharge freon; 
2   replace filter or capillary; 
3   clean the water filter and discharge the air in 
     water loop.  

Compressor do 

not run

1   power supply failure                     
2   compressor contactor broken  
3   power cable loose
4   protection on compressor  
5   wrong setting on return water temp.  
6   lack of water flow    

1   check off the power supply; 
2   replace compressor contactor; 
3   tighten the power cable;
4   check the compressor exhaust temp.;  
5   reset the return water temp.; 
6   clean the water filter and discharge the air in 
     water loop.  

High noise of 

compressor

1   liquid refrigerant goes into compressor  
2   compressor failure 
   

1   bad evaporation, check the cause for bad 
     evaporation and get rid of this;                
2   use new compressor;
   

Fan do not run

1   failure on fan relay                
2   fan motor broken  
   

1   replace the fan relay;                  
2   replace fan motor.
   

The compressor 

runs but heat 

pump has not 

heating or 

cooling capacity

 

1   no gas in the heat pump; 
2   heat exchanger broken; 
3   compressor failure.

1   check system leakage and recharge refrigerant;
2   find out the cause and replace the heat 
     exchanger; 
3   replace compressor.      
   

Low outlet water 

temperature

1   low water flow rate;
2   low setting for the desired water temp.;        
   

1   clean the water filter and discharge the air in 
     water loop.  
2   reset the desired water temperature.         
   

Low water flow

 protection  

1   lack of water in the system;
2   failure on flow switch           
   

1   clean the water filter and discharge the air in 
     water loop.  
2   replace the flow switch.         
   

23

Содержание H15A

Страница 1: ...Installation and Instruction Manual Inverter Air Source Water Heat Pump Floor heating and Air con Unit Hero Series Manual...

Страница 2: ...f heat pump 2 Choose a right heat pump unit 3 Installation place 4 Installation method 5 Water loop connection 6 Power supply connection 7 Location of the unit 8 Transit 9 Trial Running 1 Interface 3...

Страница 3: ...uded which is very easy for installation 3 Flexible installation The unit has smart structure with compact body just simple outdoor installation is needed This series of heat pump unit owns following...

Страница 4: ...n Compulsory implement The listed action need to be taken ATTENTION include WARNING Please pay attention to what is indicated Mark Notes Icon notes WARNING ATTENTION To prevent the users and others fr...

Страница 5: ...red When there is something wrong or strange smell the power supply need to be shut off to stop the unit Continue to run may cause electrical short or fire Move and repair Entrust Prohibit Entrust Whe...

Страница 6: ...check the installation basement in a period one month to avoid any decline or damage on the basement which may hurt people or damage the unit Safety Precaution Meaning Fix the unit Installation Place...

Страница 7: ...controller is 200 meters Air outlet in horizontal direction Water intlet tube Remote Controller Manually Water outlet tube 5 Air outlet in horizontal direction Water outlet tube Water intlet tube The...

Страница 8: ...nge Power Supply Compressor Quantity Compressor Model Fan Quantity Fan Power Input Fan Rotate Speed Noise Water Pump Input Max water head Water Connection Water Flow Volume External Pressure Unit Net...

Страница 9: ...ation Models H15A 1000 505 465 647 1475 Water inlet 1 1 4 Condensate outlet 1 1 4 Water outlet 3 4 Water outlet 1 1 4 Water pump wire 369 5 170 266 5 51 5 7 Models H8A Water outlet 1 Water inlet 1 980...

Страница 10: ...e and high efficiency 2 Environmentally friendly refrigerant Use the new generation of environmentally friendly refrigerant R410 which is harmless to the ozone sphere 3 Heating in frigid environment O...

Страница 11: ...ooling unit for cooling chilled water outlet temp at 5 15 maximum ambient temp at 43 For heating warm water inlet temp at 40 50 minimum ambient temp at 10 Unit application a s w h p is used for house...

Страница 12: ...ank on the top point of the water loop and the water level in the tank must be at least 0 5 meter higher than the top point of the water loop 6 Power supply connection Open the front panel and open th...

Страница 13: ...ller Check whether the water pump is running if it runs normally there will be 0 2 MPa on the water pressure meter When the water pump runs for 1 minutes the compressor will start Hear whether there i...

Страница 14: ...In the state of cooling the icon Cool is on In the state of heating the icon Hot is on 5 Fan Speed Short press Fan Speed to enter the Query interface 6 7 8 In OFF state long press ON OFF to enter the...

Страница 15: ...4 way valve status icon is on and when the 4 way valve shuts down the icon is off Inlet Inlet icon Compressor When the compressor starts up in the main display area thecompressor status icon is on and...

Страница 16: ...In the main interface long press for 1 second to switch between the cooling and heating modes Cooling Interface Heating Interface Note 1 Without Thermostat wired controller can be used for Startup Shu...

Страница 17: ...omatically record the setting and back to the main interface Note In the query parameter interface it cannot automatically back to the main interface 3 3 Temperature Short press or to enter thetempera...

Страница 18: ...perature Outlet Temperature Suction Temperature Discharge Temperature Ambient Temperature Coil Temperature Low Pressure High Pressure Electronic Expansion Valve Steps Compressor Actual Frequency Compr...

Страница 19: ...rt press for flashing by the minute Short press or to change flashing by the minute Short press back to the main interface 3 6 2 Set and cancel the timing if connected to the thermostat the timing fun...

Страница 20: ...ON OFF back to the main interface and short press UP or DOWN to display multiple errors On the main interface short press ON OFF to back to the Error Interface For 10 seconds without operation automa...

Страница 21: ...E03 E19 E20 E07 P81 E44 E21 E22 E23 blank 5 Electronic Control Error Table None DC bus over voltage protection DC bus low voltage protection IPM over current protection IPM overheating protection Radi...

Страница 22: ...GND GND GND GND GND GND GND GND GND GND GND GND GND 5V 12V GND 485_B 485_A CAN_L GND 12V CAN_H 12V GND 485_B 485_A CN1 CN2 CN7 CN3 CN4 CN9 DI5_PWM DO5_PWM DI4_PWM DO4_PWM DI3_PWM DO3_PWM DI2_PWM A02 D...

Страница 23: ...wer Live Wire Not Used Pump 4 way valve Fan Not Used Def Heating Crankshaft Heating Spray Valve Auxiliary Electric Heating Not Used Inlet Temperature Sensor Outlet Temperature Sensor Discharge Tempera...

Страница 24: ...of power component is too high Fault of current sampling Compressor current is too high Input voltage is in default phase Default phase step out or hardware damage on actuator Fault of DSP and communi...

Страница 25: ...er or capillary 3 lack of water flow 1 check the gas leakage and recharge freon 2 replace filter or capillary 3 clean the water filter and discharge the air in water loop Compressor do not run 1 power...

Страница 26: ...other modules which are indispensable fittings are provided by users or installation company 2 The unit which of code contains the letter B has water pump inside and need not install water pump outsid...

Страница 27: ...please screw down the pressure to adjust the screw B 4 When the system need fill water at first wrest the handle A of filled water Then the handle A can return close when the system is full of water...

Страница 28: ...endix 4 The way of assistant heat source connection Unit provides the connection of assistant heat source which can not be only for gas fired boiler but also for electronic boiler or warm net pipe for...

Страница 29: ...It is advised to control equipment by mobile terminal after connection to WiFi module B Connect with external water pump Note Connect frequency water pump PWM control to reserved interface as required...

Страница 30: ...life must be handled separately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Direc...

Страница 31: ...ase line MCB Creepage protector Signal line 2 n 0 5mm Nameplate maximum current Earth line No more than 10A 20A 32A 40A 40A 63A 80A 100A 125A 160A 225A 250A 280A 2 1 5mm 2 2 5mm 2 4mm 2 6mm 2 10mm 2 1...

Страница 32: ...Code 20160612 0003...

Отзывы: