6.APPENDIX
(2) Cable specification
1. Single phase unit
Nameplate
maximum
Phase line
current
No more
than 10A
2X1.5mm
2
10-16A
2X2.5mm
2
16~25A
2X4mm2
25~32A
2X6mm
2
32~40A
2
x
1
omm
2
40~63A
2X16mm
2
63~75A
2X25mm"
75~101A 2X
2
5mm
"'
101~123A
2
X35mm"
123-148A
2X50mm"
148~186A
2X70mm"
186~224A 2X95mm
2
2. Three phase unit
Nameplate
maximum
Phase line
curr,mt
No more
than 1 OA
3X1.5mm2
10~16A
3X2.5mm
2
16~25A
3X4mm
2
25~32A
3X6mm
2
32~40A
3X10mm
2
4Q-A'll\
3X16mm
2
63~75A
3X25mm
2
75~101A
3X25mm
2
101~123A
3X35mm
2
123~148A
3X50mm
2
148~186A
3X70mm
2
186~224A 3X95mm
2
Earth line
MCB
Creepage protector
Signal line
1.5mm
2
20A
30mA less than 0.1 sec
2.5mm
2
32A
30mA less than 0.1 sec
4mm
2
40A
30mA less than 0.1 sec
6mm
2
40A
30mA less than 0.1 sec
10mm
2
63A
30mA less than 0.1 sec
16mm"
80A
30mA less than 0.1 sec
nX0.5mm
2
25mm"
100A
30mA less than 0.1 sec
25mm
2
125A
30mA less than 0.1 sec
35mm
2
160A
30mA less than 0.1 sec
50mm
2
225A
30mA less than 0.1 sec
70mm
2
250A
30mA less than 0.1 sec
95mm
2
280A 30mA less than 0.1 sec
Earth line
MCB
Creepage protector
Signal line
1.5mm
2
20A 30mA less than 0.1 sec
2.5mm
2
32A 30mA less than 0.1 sec
4mm
2
40A
30mA less than O. 1 sec
6mm
2
40A
30mA less than 0.1 sec
10mm
2
63A
30mA less than 0.1 sec
16mm
2
BOA
30mA less than 0.1 sec
nX0.5mm
2
25mm
2
100A
30mA less than 0.1 sec
25mm
2
125A
30mA less than 0.1 sec
35mm
2
160A
30mAless than 0.1 sec
50mm
2
225A
30mA less than O .1 sec
70mm
2
250A
30mA less than 0.1 sec
95mm
2
280A
30mAless than 0.1 sec
If the unit is installed outdoors, please use a cable which guards against UV.