Prior to Trial Operation 

Check the indoor unit, make sure that the pipe connection is done correctly and that the relevant valves are open. 

Check the water loop to ensure that there is enough water inside of the expansion tank, that the water supply is good 

and that the water loop has no air in it and is full of water. Make sure there in good insulation for the water pipe. 

Check the electrical wiring. Make sure that the power voltage is normal, the screws are fastened, the wiring is made in 

line with the diagram and the earthing is connected. 

Check that the heat pump, including all the screws and different parts are in good order. When the power is on, review 

the indicator on the controller to see if there is any failure indications. The gas gauge can be connected to the check 

valve to see the high pressure (or low pressure) of the system during trial running. 

 

3.8

 

Trial Operation 

Start the heat pump by pressing the “ 

 or

 

 “ key on the controller. Check whether the water pump is running, if 

it is running normally there will be 0.2MPa on the water pressure meter. 

When the water pump rungs for 1 minute, the compressor will start. Hear whether there is a strange sound coming 

from the compressor. If an abnormal sound occurs, please stop the unit and check the compressor. If the compressor 

runs well, look for the pressure meter of the refrigerant. 

Check whether the power input and running current is in line with the manual. If not stop the unit and check for why 

this may be occurring. 

Adjust the valves on the water loop to make sure that the hot (cool) water supply to each door is good and meets the 

requirement of heating (or cooling). 

Review whether the outlet water temperature is stable. 

The parameters of the controller are set by the factory, the user must not change these. 

 

3.9

 

Maintenance 

Check the water supply and the air vent frequently to avoid lack of water or air in the water loop. 

Clean the water filter periodically to keep the water good quality. Lack of water and dirty water can damage the unit. 

The heat pump will start the water every 72 hours when it is not running to avoid freezing. 

Keep the unit in a clean, dry place with good ventilation. Clean the heat exchanger every few months to keep a good 

heat exchange rate and save energy. 

Check each part of the unit and the pressure of the system. Replace any failing parts and recharge the refrigerant if 

needed. 

Check the power supply and the electrical system, make sure all electrical components are wired well and working.  

If the heat pump is not to be used for an extended period of time, please drain all the water out. Drain the water out 

from the lowest point of the heat exchanger to avoid freezing in winter. Water recharge and full inspection on the heat 

pump is needed before being restarted. 

The water loop of the heat pump MUST be protected from freezing in winter. Do not shut off the power supply to the 

heat pump in winter. When the air temperature is below 0°C, if the inlet water temperature is above 2°C and below 4°C 

the water pump will begin freezing protection. If the inlet water is lower than 2°C, the heat pump will begin heating. 

Содержание EVO MAX 32

Страница 1: ...P a g e 1...

Страница 2: ...ntrolling and Operation 12 4 1 Controller Display 12 4 2 How to Use the Controller 13 4 2 1 Power On 13 4 2 2 Check Parameters 13 4 2 3 Temperature Settings 14 4 2 4 Malfunctions 15 4 3 Parameter Tabl...

Страница 3: ...stalled or repaired by a qualified installer and authorised dealer Maintenance and operation should be carried out according to the recommended frequency Only genuine standard spare musts must be used...

Страница 4: ...Compressor Quantity 1 Fan Quantity 2 Fan Motor Input W 260x2 Circulation Pump Grundfos Water Flow Volume m3 h 5 Water Pressure Drop kPa 46 Suggested Water Temp Differential C 5 Water Connection inch...

Страница 5: ...P a g e 5 2 2 Unit Dimensions Evo Max 32...

Страница 6: ...rs and others from being harmed while using this unit to avoid damage to the unit and for to prevent improper use ensure that the following information is understood The piping connection and wiring s...

Страница 7: ...P a g e 7...

Страница 8: ...P a g e 8...

Страница 9: ...ITH HANDS OR OBJECTS 3 3Installation Notes The unit can be installed in any outdoor area which can carry heavy machinery such as a terrace rooftop the ground etc The location must have adequate ventil...

Страница 10: ...Thread the power line though the hole and connect it to the power line terminal The three core control line of the remote controller shall be plugged with the three core signal line on the main board...

Страница 11: ...ck for why this may be occurring Adjust the valves on the water loop to make sure that the hot cool water supply to each door is good and meets the requirement of heating or cooling Review whether the...

Страница 12: ...P a g e 12 4 Controlling and Operation 4 1 Controller Display...

Страница 13: ...P a g e 13 4 2 How to Use the Controller 4 2 1 Power On 4 2 2 Check Parameters...

Страница 14: ...P a g e 14 4 2 3 Temperature Settings...

Страница 15: ...E3 The sensor is open or short circuit Check or change sensor Ambient sensor failure E4 The sensor is open or short circuit Check or change sensor Anti freezing under cooling mode A1 Water flow rate n...

Страница 16: ...07 0 not present 1 NTC Cond Probe 2 NTC Out Probe 3 Differential Control Probe Int 0 D03 Start Defrosting Temperature C 2 D04 End Defrost Pressure C 13 F02 Fan Operating Mode 0 Always ON 1 2 3 Int 2...

Страница 17: ...System 2 economizer outlet temp failure 02 P202 The sensor is open or short circuit Check or change the sensor System 1 anti freeze protection 71 P19 Water flow volume is not enough Check the flow vol...

Страница 18: ...03 System 1 alert inlet 220 230VAC 8 CC04 System 2 alert inlet 220 230VAC 9 NET GND 12V Wire Controller 10 DI01 GND Mode Communication 11 AI01 GND System 1 anti freeze temp input 12 AI02 GND System 2...

Страница 19: ...on Block on filter or capillary Replace filter or capillary Lack of water flow Clean the water filter and discharge the air in water loop Compressor does not run Power supply failure Check off the pow...

Страница 20: ...f its useful life must be handled separately from domestic waste and must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent...

Страница 21: ...0A 30mA less than 0 1 sec 186 224A 2 x 95mm 95mm 180A 30mA less than 0 1 sec 6 2 2 Three Phase Unit Nameplate max current Phase Line Earth Line MCB Creepage Protector Signal Line No More than 10A 3 x...

Отзывы: