6.Usage

6.2.7 Keyboard lock

     To avoid mis-operations, please lock the controller after parameter setting.
    At the main interface, pressing 

     

for 5 seconds

the keyboard will be locked.

    When the keyboard is locked, pressing

     

for 5 seconds, the keyboard will be unlocked.

NOTES: 
When the unit is in alarming state, the key lock can be removed automaticly.

Press

     

Locked

6.2.8  Malfunction display

 

There will be malfunction code showing on the controller screen when relative malfunction 
occurs.
 You can refer to the malfunction table to find out the failure cause and solution.
  For example

              P01
    Inlet water temp.
     Failure

Failure number

1

Malfunction code

Malfunction

Failure number
press

   

or

   

can check 

next malfunction

Parameter table

Meaning

Set-point of heating target temp. 

Default Remarks

Ajustable

70

ON

Heating

Inlet temp.:                35.0

Outlet temp.:             65.0

2015/07/20 05:55 MON.

ON

Heating

Inlet temp.:                35.0

Outlet temp.:             65.0

2015/07/20 05:55 MON.

7.1  Malfunction table

Power on

P01

P02

P15(system1),P25(system2)
P35(system3),P45(system4)

P04

Malfunction

Display

Reason 

Resolution

Normal working

Outlet temp. Sensor failure

Inlet temp. Sensor failure

You can refer to the malfunction table to find out the failure cause and solution.

Water flow is not enough 
and low differential pressure

Communication failure between 
wire controller and main board

The protection system is failure

Water flow is not enough

The ambient temp. Is low

No water/little water in water
 system

The high-preesure switch is broken

Electrical-heat is over heat

The temp. Sensor is broken or 

short circuit

Check or change the   temp. Sensor

Check or change the   temp. Sensor

Check or change the   temp. Sensor

Check or change the   temp. Sensor

Check or change the   temp. Sensor

Check or change the   temp. Sensor

Check or change the   temp. Sensor

Check or change the   temp. Sensor

The low-preesure switch is broken

Water flow is not enough

The ambient temp. Is low

Check the pressure switch and cold circuit

Check the pressure switch and cold circuit

Check the pipe water flow and water pump

Check or change electrical-heat

Check the pipe water flow and whether 
water system is jammed or not 

Check the pipe water flow and whether 
water system is jammed or not 

Check the pipe water flow and whether 
water system is jammed or not 

Check each protection point of the system

Check the wire connection  between 
remote wire controller and main board 

/

/

The temp. Sensor is broken or 

short circuit

The temp. Sensor is broken or 

short circuit

The temp. Sensor is broken or 

short circuit

The temp. Sensor is broken or 

short circuit

The temp. Sensor is broken or 

short circuit

The temp. Sensor is broken or 

short circuit

The temp. Sensor is broken or 

short circuit

Ambient  temp. Failure

System 1/2/3/4 
Coil temp. Failure

System 1/2/3/4 absorb 
Temp. Failure

System 1/2/3/4 anti-freeze 
Temp. Failure

Using side system 1 /2/3/4
Anti-freeze temp. Failure

System 1/2/3/4 coil inlet 
Temp. Failure

System 1/2/3/4 high 
Pressure protection

System 1/2/3/4 low 
Pressure protection

Water flow failure

Electric-heater 
Overheat protection

Water inlet and outlet 
Temp. Too big

System 1/2/3/4 anti-freeze 
Protection

System 1/2/3/4 source side 
Anti-freeze protection

System 1/2/3/4 using side 
Anti-freeze protection

Anti-freeze protect  level 1

Anti-freeze protect  level 2

System protection

Communication failure

P17(system1),P27(system2)
P37(system3),P47(system4)

P19(system1),P29(system2)
P39(system3),P49(system4)

P191(system1),P291(system2)
P391(system3),P491(system4)

P151(system1),P251(system2)
P351(system3),P451(system4)

E11(system1),E21(system2)
E31(system3),E41(system4)

E12(system1),E22(system2)
E32(system3),E42(system4)

E03

E04

E06

E06

E17(system1),E27(system2)
E37(system3),E47(system4)

E171(system1),E271(system2)
E371(system3),E471(system4)

E19

E29

E05

E08

Water flow is not enough 
and low differential pressure

Check the pipe water flow and whether 
water system is jammed or not 

7.Maintenance and inspection

27

Содержание ALLHT1170R134

Страница 1: ...AIR SOURCE WATER HEAT PUMP HIGH TEMPERATURE UNITS Installation Instruction Manual Polaris MT 70 Manual...

Страница 2: ...tration 8 3 Appendix Marking Description Icon Description Performance Parameter List Outline Dimensional Drawing Unit Function Description Installation Space Installation Schematic Diagram Model Selec...

Страница 3: ...the contractor If the heat pump unit can just be installed a while latter please keep it free from damage rust or abrasion by following methods 1 all the access like the water connections must be sea...

Страница 4: ...warning Detailed cautions are represented by graphics or words in or near the icon To prevent the user himself or others from personal and property damage and ensure correct and safe use of the unit p...

Страница 5: ...ury When abnormal conditions burning smell occur immediately cut off the manual power switch to stop running and contact the dealer Continuing abnormal conditions may cause electric shock or fire Movi...

Страница 6: ...iron wires are used it may cause malfunction or fire Do not spray the combustible spray directly to the outdoor unit otherwise this may easily Installation precaution Do not install it in a place wher...

Страница 7: ...Model Recycled heating 2 2000 2 920 75 380V 3N 50Hz Subject to data on the package Nameplate W RPM dB A mm mm kg kg Power Supply Scroll Compressor Type 4 Compressor Quantity Fan Quantity Fan power inp...

Страница 8: ...mensional Drawing 3 Specification Air out direction Installation Bottom Outlet Water outlet DN80 flange Electrical control box 4 16 2030 2180 900 900 1080 1020 400 175 530 Water inlet DN80 flange Mode...

Страница 9: ...e the heating efficiency it will last 2 10 minutes Working condition In order to use the unit correctly please run the unit at environment temperature 7 43 The unit includes sophisticated electronic d...

Страница 10: ...ater Return Pipe 9 10 11 12 13 5 1Installation Space 2180 2180 2180 2180 3160 5240 7320 9400 2030 2030 2030 2030 Dimensions Outline Dimensional Drawing Parallel Units Schematic Diagram of Unit Install...

Страница 11: ...unit 4 Application occasions 5 4Selection of the Installation Position The unit can be installed on balconies roofs floors or any other places easy to install and reliable for load bearing Air circul...

Страница 12: ...e installation base place shockproof rubber pads on the ground or the roof and ensure that the unit is placed levelly Air out direction 1500mm Figure 1 Installation Schematic Diagram of Snow Shed To e...

Страница 13: ...inspection during operation Drainage interfaces should be installed at all low positions of the water system the unit has a drain port to facilitate drainage interfaces will be added in other position...

Страница 14: ...V Three core signal line 2 3 0 5mm Notes 1 The unit uses the three phase power supply and the cable specification in the table above refers to the cable specification of each phase 2 1 Both the neutra...

Страница 15: ...of water and whether the air is completely exhausted Check whether all valves in the system are opened Check whether the pipelines are well insulated Check the power distribution system Check whether...

Страница 16: ...he sense of hearing if there is any abnormal sound immediately cut off the power and check the unit if there is no abnormal sound continue the operation and then note whether the pressure of the refri...

Страница 17: ...n to confirm current operation ON OFF Press this button to start up shut off the unit cancel current operation or back to upper interface HELP MODE CLOCK Button Name Function 6 1 Function of wire cont...

Страница 18: ...up 2 Pressing this key could select the upward option or increase the value of a certain parameter 3 Pressing this key could select the downward option or decrease the value of a certain parameter 4...

Страница 19: ...and shutting down Press in the shutdown state for 1s to start up the system Press in the startup state for 1s to shut down the system For example Press for 1s Running state MODE By actual state Month...

Страница 20: ...ut Press T01 Inlet water 55 0 T02 Outlet water 65 0 T03 Ambient 30 5 T04 Coil 1 30 5 T05 Coil 2 45 5 T06 Suction L1 65 5 T07 Suction H1 25 5 T08 Deice 1 65 5 Press Press Press ON Heating Inlet temp 25...

Страница 21: ...nter clock setting interface select the needing parameter and press at this time parameter value flashing press increasing or Decreasing can change parameter value then press to save press can cancel...

Страница 22: ...automatic and back to the main interface As follow Date 16 07 2016 Time 05 55 Week Thursday Timer Date format Date 16 07 2016 Time 05 55 Week Thursday Timer Date format Date 16 07 2016 Time 06 55 Wee...

Страница 23: ...lock setting For example Hour bit flashing No operation in 10s It has been changed Press to enter clock interface Press to select Timer Timer zone Daily timer Press to enter Timer interface A Timer se...

Страница 24: ...0 Timer2 00 00 00 00 Timer3 00 00 00 00 Timer4 00 00 00 00 Timer1 07 00 00 00 Timer2 00 00 00 00 Timer3 00 00 00 00 Timer4 00 00 00 00 Timer1 07 00 00 00 Timer2 00 00 00 00 Timer3 00 00 00 00 Timer4 0...

Страница 25: ...ce Press to select Timer Press to enter timer interface B The operation of daily timer Press Timer1 07 30 22 00 Timer2 00 00 00 00 Timer3 00 00 00 00 Timer4 00 00 00 00 Timer zone Daily timer Date 16...

Страница 26: ...Timer4 Sat Timer2 Timer4 Sun OFF Mon Timer1 Tue Timer1 Timer3 Wed ON Thu Timer3 Timer1 Fri Timer4 Sat Timer2 Timer4 Sun OFF Mon Timer1 Tue Timer1 Timer3 Wed ON Thu Timer3 Timer1 Fri Timer2 Sat Timer2...

Страница 27: ...then it will be running the whole day on Monday and vice versa Wednesday ON means system will be running the whole day on Wednesday Thursday OFF means system will be off the whole day on Thursday Satu...

Страница 28: ...2 8 Malfunction display There will be malfunction code showing on the controller screen when relative malfunction occurs You can refer to the malfunction table to find out the failure cause and soluti...

Страница 29: ...the wire connection between remote wire controller and main board The temp Sensor is broken or short circuit The temp Sensor is broken or short circuit The temp Sensor is broken or short circuit The t...

Страница 30: ...10 RO 11 GND NET 12V 5V 0 10V GND GND AI 01 AC12V AC12V RS485B RS485A AI 02 AI 03 AI 04 AI 05 AI 06 AI 07 AI 08 AI 09 AI 10 AI 11 AI 12 AI 13 AI 14 AI 15 AI 16 DI 01 DI 02 DI 03 DI 04 DI 05 DI 06 DI 0...

Страница 31: ...03 GND AI04 GND AI05 GND AI06 GND AI07 GND AI08 GND AI09 GND System 2 exhaust temp input System 1 exhaust temp input System 2 economizer inlet temp failure input System 1 economizer inlet temp failure...

Страница 32: ...e handled separately from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 9...

Страница 33: ...ely from domestic waste must be taken to a recycling centre for electric and electronic devices or handed back to the dealer when purchasing an equivalent appliance 6 Directive 2002 95 EC RoHs This pr...

Страница 34: ...line MCB Creepage protector Signal line 2 n 0 5mm Nameplate maximum current Earth line No more than 10A 20A 32A 40A 40A 63A 80A 100A 125A 160A 225A 250A 280A 2 1 5mm 2 2 5mm 2 4mm 2 6mm 2 10mm 2 16mm...

Страница 35: ...Note...

Страница 36: ...Code 20170803 0003...

Отзывы: