32
according to the dosage indicated below:
To guarantee the ModuSat TP, Evinox insists that only its own heating system water
conditioning products are used:
- BIONIBAL corrosion inhibitor
- BIONIBAGEL antifreeze and corrosion inhibitor.
IMPORTANT WARNING:
Bionibal or Bionibagel must only be put in a clean installation that has been checked. It is
therefore imperative to fill the entire system one or more times with clean water as
required. In some cases, the system may need washing by a suitable product:
SUGGESTED DOSE:
-
1 litre every 100 litres of the radiator circuit capacity
-
1 litre every 100 litres of the under floor heating circuit capacity with oxygen blocking
barrier pipes
-
2 litres every 100 litres of the under floor heating circuit capacity without oxygen
blocking barrier pipes.
Over dosage doesn’t cause damage to the circuits.
Restore the correct concentration every time the circuit is emptied.
4.6 Freeze prevention
In case it is necessary to guarantee frost as well as corrosion prevention,
IT IS
ADVISABLE
to use
BIONIBAGEL,
as this is compatible with BIONIBAL (except when
different directives are given for boiler protection)
BIONIBAGEL
has specifically been developed to be used in circuits treated with
BIONIBAL or as a multi-function fluid for new installations.
The following table indicates the percentage of additive to use according to the protection
temperature chosen.
Protection temperature
Circuit capacity
50
100
150
200
- 5 °C
7
15
22
30
- 10 °C
12
25
37
50
- 15 °C
17
35
50
70
- 20 °C
20
40
60
80
- 30 °C
22
45
67
90
4.7 Unit filling
The DHW circuit must be filled and pressurised before applying pressure to the primary
circuit. In order to guarantee the safety and correct functioning of the unit, the start up
must be carried out by qualified technical personnel.
To fill the DHW circuit proceed as follows:
-
open the heating circuit ball valves in the unit
-
release the air contained by opening the relief valve