3.3 Hydraulic connections
The ModuSat TP is designed to be wall mounted with the primary circuit and domestic
water hydraulic connections as shown here below.
In order to ease the installation and maintenance of the unit, it is recommended to follow
the instructions about minimum spacing.
Connection to the heating circuit
The primary circuit must be equipped with:
Al the devices indicated in the current norms
One or more pumps suitable to handle the pressure drops on the primary circuit, in
order to guarantee the proper operation of all modules.
The circuit must be filled with clean water. Refer to EVINOX technical office for
approved additional products.
The apartment circuit must guarantee the sufficient and correct flow of fluid into the
module.
The safety valve drain must be connected to a tundish that allows a visual check
in order to prevent, in case of activation, damage to people, animals and objects
that cannot be attributed to the manufacturer or to the supplier.
Minimum space requirements for access and servicing:
Front: 700 mm
Side: 50 mm
Bottom: 400 mm