Running the Pump for Secondary System Commissioning
The commissioning switch is located inside the ModuSat® case next to the manometer and heat
meter display.
This switch enables the unit to be put into a
manual heating ‘on’ mode prior to full unit
commissioning to enable the testing of the
secondary / apartment heating circuit.
Please note that this function should not be
used until the secondary installation is
complete i.e. flushed, treated and refilled to
the correct pressures.
To enable the heating run mode setting the
button should be depressed and held in for
approximately 30 seconds. The heating PICV
will open. The unit will then run at a pre-set
ouXRut temperature of 45°C thus providing a
safe temperature for UFH circuits and also a
gentle warm up of radiator circuits. This
function will run for a pre-set period of
approximately 45minutes.
Rocket-Switch
Please note: The rocker switch below the commissioning push button is the Pump
Manual Override. This should NOT be operated or used by persons other than
Evinox Energy engineers as it is for fault diagnostic use only.
Setting unit into operation
6.3.1
Pressure independent control valve
DHW PICV
HTG PICV
Maximum flow rate
1450 l/h +/- 10%
500 l/h +/- 10%
Start up ∆P
25 kPa
25 kPa
Max differential ∆P
400 kPa
400 kPa
Valve size
DN20
DN15
Thread
G1
G 3/4’’
Actuator Stroke
2.5 mm
2.5 mm
Actuator control signal
0-10V
0-10V
Mechanical pre-setting
Not available
Available
Commissioning
Switch
Pump Manual
Override Rocker