18
2551868A
First fill of the system
Clean and flush the system before connecting the unit.
Filling the system should be performed only after the system has been fully
flushed and clean. Poor water quality may cause failure of the operation of the
unit.
Water quality.
It is recommended that the flushing and cleaning of the primary circuit, domestic
water circuit and secondary heating circuit is performed by a qualified person in
accordance with current standards, regulations and BSRIA guidelines.
In the case of a water leak.
Take caution of hot water
Slowly close the isolation valve at the top of the unit
Contact Evinox Energy
The ModuSat® pump should not be used for flushing.
The pump is integral to the unit and should not be used for flushing and cleaning
the system. Failure to meet this requirement will invalidate the warranty.
Filling the primary circuit
Please take care when filling the ModuSat® unit.
Slowly close the by-pass while the
isolation valves are in the closed
position
Slowly open the isolation valves on
the primary circuit to the design
pressure.
Visually check that there are no
leaks. Tighten the connections of
the valve kit if necessary.
If there is a leak internal to the unit,
ensure the isolation valves are left
in a closed position.
First fill of apartment heating system
The ModuSat® unit is fitted with a manometer gauge that is mounted in the front panel. This gauge
reading should be used when filling the secondary circuit.
An external filling loop should be used for filling the secondary
circuit with the mains water.
Open the isolation valves slowly when filling the system.
Cold fill should be done to about 1.5 bar in a single-story
dwelling. The pressure required will depend on the head of
the system (difference between the lowest and highest point).
Once the required pressure is reached, close the filling loop
ball valve, vent the system and repeat it again.