background image

E2608 series Modbus holding registers (part 3)
Register addresses are shown 0-based, Addr in hexadecimal, Reg in decimal format.
Modbus holding register numbers MHR are shown in decimal 1-based format, and may be addressed either from 00001 or 40001 base.

Addr

Reg / MHR RW

Description

Supported values (dec)

Default

0x00DB

219 / 40220 RW

Control logic for relay RE1

0 – none
1 – relay on at high values
2 – relay on at low values
3 – relay on at values within the range
4 – relay on for the values out of the range

0

0x00DC

220 / 40221 RW

Control logic for relay RE2

0 – none
1 – relay on at high values
2 – relay on at low values
3 – relay on at values within the range
4 – relay on for the values out of the range

0

0x00DD

221 / 40222 RW

LOW setpoint for relay RE1

0...65535 (gas units)

see

Specifications

0x00DE

222 / 40223 RW

HIGH setpoint for relay RE1

0...65535 (gas units)

see

Specifications

0x00DF

223 / 40224 RW

LOW setpoint for relay RE2

0...65535 (gas units)

see

Specifications

0x00E0

224 / 40225 RW

HIGH setpoint for relay RE2

0...65535 (gas units)

see

Specifications

0x00FF

255 / 40256 RW

Sensor, analog outputs, LED and buzzer status

bit[0]=0/1 – sensor present/absent, read-only!
bit[1]=0/1 – analog outputs deactivated/activated,
bit[2]=0/1 – in case the sensor is absent, turn signaling off/on analog output1,
bit[3]=0/1 – in case the sensor is absent, turn on signaling with low current/high
current on analog output1; if bit[2]==0 this bit will be ignored
bit[4]=0/1 – in case of sensor absent, turn signaling off/on analog output2
bit[5]=0/1 – in case of sensor absent, turn on signaling with low current/high current
on analog output2; if bit[4]==0 this bit will be ignored
bit[6]=0/1 – current/voltage output detected on output1, read-only!
bit[7]=0/1 – current/voltage output detected on output2, read-only!
bit[8]=0/1 – LED deactivated/activated
bit[9]=0/1 – buzzer deactivated/activated
bit[10]=0/1 – LED is on/off in normal condition
bit[11]=0/1 - 1 Hz (50% on, 50% off) LED signal off/on if relay1 turned on
bit[12]=0/1 - 2 Hz (50% on, 50% off) LED signal off/on if relay2 turned on

user defined

0x0101

257 / 40258

R

Raw gas sensor data

0...4095, ADC units

0x0102

258 / 40259

R

Measured temperature, °C×100

signed integer, -4000...+12500 (-40,00...+125,00 °C)

0x0103

259 / 40260

R

Gas concentration, gas units

0...65535, gas units

0x0105

261 / 40262 RW

0% value for analog output 1

-32000...+32000 (gas unit/°C)

user defined

0x0106

262 / 40263 RW

100% value for analog output 1

-32000...+32000 (gas unit/°C)

user defined

0x0107

263 / 40264 RW

0% value for analog output 2

-32000...+32000 (gas unit/°C)

user defined

0x0108

264 / 40265 RW

100% value for analog output 2

-32000...+32000 (gas unit/°C)

user defined

* — The new value is applied after restart.
** — Broadcast slave ID 0 can be used to assign a new ID to device with unknown ID. When addressing by ID 0 the device shall be the only Modbus instrument in the network.

The device will not respond to Master command when addressed by ID 0.

*** — This value is dynamic and not kept in EEPROM after restart

NOTE 2 

Sensor absense signalling (bits from [2] to [5]) is available only

for sensors with digital interface ( e.g.-CO2 10K, -O2-L).
NOTE 3

 LED/buzzer signalization (if activated):

Detectable sensor
absence or malfunction

0.5Hz (90% off, 10% on) light and/or sound
signal

Relay1 turned on

1 Hz (50% on, 50% off) light and/or sound
signal, depending on bit[8], bit[9] and bit[11]

Relay2 turned on

2 Hz (50% on, 50% off) light and/or sound
signal, depending on bit[8], bit[9] and bit[12]

Modbus response

the light signal is modulated with short on-off
pulses, even single Modbus cycle is visible

Normal operating

continuously on/off depending on bit[10]

NOTE 4

 We recommend to set the difference between the upper and

bottom limits of the output scale not narrower than 20% of detection
range (for CO detectors the scales down to 5% of range are allowed). In
any case, do not set the output scale below the tenfold resolution of the
device.

NOTE 1

 Relay setpoints should be set within 5-95% of the detection

range.

Содержание PluraSens E2608-NO

Страница 1: ...be versions E2608 NO_UM_EN Rev 06 06 2020 Specifications Sensor type electrochemical cell Sampling method diffusion Typical detection range 0 250 ppm Maximum overload 1000 ppm Resolution digital unit 1 ppm Response time T90 40 s Sensor lifetime 12 months Calibration interval 6 months Signal update every 1 second Power supply options 11 30 VDC 24 VAC or 90 265 VAC with mains power unit Power consum...

Страница 2: ...s devices are suitable for a wide range of wires with cross section 0 2 1 5 mm2 We recommend to strip the wire end by 8 9 mm and use wire end sleeves To connect the wire insert the wire end into terminal hole To disconnect push the spring loaded terminal lever pull the wire out and release the lever Use twisted pair cable e g LiYY TP 2 2 0 5 mm2 or CAT 5 to connect the device to RS485 network Resp...

Страница 3: ... or 40001 base Addr Reg MHR RW Description Supported values dec Default 0x0001 1 40002 R Hardware version 0x0002 2 40003 R Software version 0x0003 3 40004 R Product serial number 1 65535 0x0004 4 40005 RW Slave ID net address 1 247 1 0x0005 5 40006 RW Baudrate 1200 2400 4800 9600 19200 38400 57600 9600 0x0006 6 40007 RW Response delay ms 1 255 10 0x0007 7 40008 RW Stop bits parity bit 1 no parity ...

Страница 4: ...t in reg 204 2 0x00CB 203 40204 RW Forced value for analog output 1 0 1000 0 0 100 0 of output scale 0 0x00CC 204 40205 RW Forced value for analog output 2 0 1000 0 0 100 0 of output scale 0 0x00D3 211 40212 RW Parameter tied to relay RE1 0 none 1 temperature 2 gas concentration 9 control by Modbus control state set in MHR 40214 2 0x00D4 212 40213 RW Parameter tied to relay RE2 0 none 1 temperatur...

Страница 5: ... is on off in normal condition bit 11 0 1 1 Hz 50 on 50 off LED signal off on if relay1 turned on bit 12 0 1 2 Hz 50 on 50 off LED signal off on if relay2 turned on user defined 0x0101 257 40258 R Raw gas sensor data 0 4095 ADC units 0x0102 258 40259 R Measured temperature C 100 signed integer 4000 12500 40 00 125 00 C 0x0103 259 40260 R Gas concentration gas units 0 65535 gas units 0x0105 261 402...

Отзывы: