background image

E2608_UM_EN. Annex 1. E2608 series Modbus RTU Communication Reference

RS485 communication interface

Databits: 8
Parity: none / odd / even
Stop bits: 1 or 2
Protocol: Modbus RTU

Supported Modbus functions:
03 - read multiple registers
06 - write single register

Communication parameters

Parameter

Permitted values

Default

Supported
baudrates

1200, 2400, 4800, 9600, 19200,
38400, 57600

9600

Data bits

8

8

Parity

none / odd / even

none

Stop bits

1, 2

1

Protocol

Modbus RTU

Modbus functions

03 – read multiple registers
06 – write single register

Error codes

01 – illegal function
02 – illegal data address
03 – illegal data value
04 – slave device failure (details of last error 04
can be read from register 0x0008)

E2608 series Modbus holding registers
Register addresses are shown 0-based, Addr in hexadecimal, Reg in decimal format.
Modbus holding register numbers MHR are shown in decimal 1-based format, and may be addressed either from 00001 or 40001 base.

Addr

Reg / MHR

RW

Description

Supported values (dec)

Default

0x0001

1 / 40002

R

Hardware version

-

0x0002

2 / 40003

R

Software version

-

0x0003

3 / 40004

R

Product serial number

1...65535

-

0x0004

4 / 40005

RW

Slave ID (net address) *

1...247 **

1

0x0005

5 / 40006

RW

Baudrate *

1200, 2400, 4800, 9600, 19200, 38400, 57600

9600

0x0006

6 / 40007

RW

Response delay, ms

1...255

10

0x0007

7 / 40008

RW

Stop bits, parity bit *

1 – no parity bit, 1 stop bit (default after factory reset)
2 – no parity bit, 2 stop bits
3 – odd parity, 1 stop bit
4 – even parity, 1 stop bit
NOTE

: 3 and 4 are available starting from the Software version 0x218 (dec. 536)

1

0x0008

8 /40009

R

Last error code

1...255

-

0x0011

17 / 40018

RW

Technological: age of data in seconds (read) /
restart(write)

0...65535 s (read), 42330(write)
writing 42330 restarts the device

-

* — The new value is applied after restart.
** — Broadcast slave ID 0 can be used to assign a new ID to device with unknown ID. When addressing by ID 0 the device shall be the only Modbus instrument in the network.

The device will not respond to Master command when addressed by ID 0.

*** — This value is dynamic and not kept in EEPROM after restart

Содержание PluraSens E2608-NO

Страница 1: ...be versions E2608 NO_UM_EN Rev 06 06 2020 Specifications Sensor type electrochemical cell Sampling method diffusion Typical detection range 0 250 ppm Maximum overload 1000 ppm Resolution digital unit 1 ppm Response time T90 40 s Sensor lifetime 12 months Calibration interval 6 months Signal update every 1 second Power supply options 11 30 VDC 24 VAC or 90 265 VAC with mains power unit Power consum...

Страница 2: ...s devices are suitable for a wide range of wires with cross section 0 2 1 5 mm2 We recommend to strip the wire end by 8 9 mm and use wire end sleeves To connect the wire insert the wire end into terminal hole To disconnect push the spring loaded terminal lever pull the wire out and release the lever Use twisted pair cable e g LiYY TP 2 2 0 5 mm2 or CAT 5 to connect the device to RS485 network Resp...

Страница 3: ... or 40001 base Addr Reg MHR RW Description Supported values dec Default 0x0001 1 40002 R Hardware version 0x0002 2 40003 R Software version 0x0003 3 40004 R Product serial number 1 65535 0x0004 4 40005 RW Slave ID net address 1 247 1 0x0005 5 40006 RW Baudrate 1200 2400 4800 9600 19200 38400 57600 9600 0x0006 6 40007 RW Response delay ms 1 255 10 0x0007 7 40008 RW Stop bits parity bit 1 no parity ...

Страница 4: ...t in reg 204 2 0x00CB 203 40204 RW Forced value for analog output 1 0 1000 0 0 100 0 of output scale 0 0x00CC 204 40205 RW Forced value for analog output 2 0 1000 0 0 100 0 of output scale 0 0x00D3 211 40212 RW Parameter tied to relay RE1 0 none 1 temperature 2 gas concentration 9 control by Modbus control state set in MHR 40214 2 0x00D4 212 40213 RW Parameter tied to relay RE2 0 none 1 temperatur...

Страница 5: ... is on off in normal condition bit 11 0 1 1 Hz 50 on 50 off LED signal off on if relay1 turned on bit 12 0 1 2 Hz 50 on 50 off LED signal off on if relay2 turned on user defined 0x0101 257 40258 R Raw gas sensor data 0 4095 ADC units 0x0102 258 40259 R Measured temperature C 100 signed integer 4000 12500 40 00 125 00 C 0x0103 259 40260 R Gas concentration gas units 0 65535 gas units 0x0105 261 402...

Отзывы: