background image

Configuration Parameter # 3. 
 
This parameter can be configured with the value of 0 through 127, where 0 means 
power saving being enabled and others mean power saving being disabled. 
 
PS : As long as the batteries have been refitted, the Detector will enable the power 
saving function automatically.   
 

Configuring the Phase Level of ON Command 

 
The Configuration parameter that can be used to adjust the phase level of ON 
command is transmitted is Configuration Parameter # 1. This parameter can be 
configured with the value of 0 through 127. 
 
Value        0: Set Device OFF(0x00) 
Value     1-99: Set Device On (1-99) 
Value    100-127: Set Device On to the last phase (0xFF) 
 

Note: 

0xFF means the device will be on to the last phase before the device was 

turned off. 
 

Wakeup Command Class 
 

SP103 will send a Wakeup Notification Command if it has been included into a 
Z-Wave network. The prerequisite is the connected Z-Wave controller needs to emit 
a node ID and wakeup time interval to the Detector.

 

 

The SP103 will wake up every 4 hours (default) and resend the Wakeup Notification 
Command unless configured for another time interval. The SP103 will stay awake 
for 10 seconds and then go back to sleep to conserve battery life. 
 
The time interval between Wakeup Notification Commands can be adjusted if you 
have a device in which that is supported. Refer to that device’s instructions.    The 
time interval of Wakeup Notification Commands is counted on the basis of minute 
and minimum criterion is one minute.    For instance, please always enter 60, 120, 
or 180 seconds etc. all of which are equivalent to 1, 2 and 3 minutes respectively. 
The time interval of wakeup cannot be entered 59, 61, 119, 121, 179 or 181 
seconds. 
 

Troubleshooting 

 

Symptom Possible 

Cause 

Recommendation 

Cannot carry out 
inclusion and association

1.  Run out of battery 

power 

2.  Check if reverse 

battery polarity 

3.  Check if the detector 

is out of order 

1.  Replace a new 

battery 

2.  Refit the battery with 

correct polarity 

3.  Ensure the detector is 

working properly 

Cannot control the 
connected modules 

1.  Run out of battery 

power 

2.    Check if the detector 

is out of order 

1.  Replace a new 

battery 

2.  Ensure the detector is 

working properly 

The detector not working 

1.  Run out of battery 

power 

2.  Check if the mounting 

location is proper 

3.  Check if the detector 

is mounted above a 
radiator or heater 

4.  Check if the detector 

is out of order 

1.  Replace a new 

battery 

2. Reposition 

its 

mounting location 

3.  Remove the source of 

interference or 
reposition its 
mounting location 

4.  Ensure the detector is 

working properly 

 
Specifications 
 

Battery 

1.5V AAA size x 2 

Range 

Up to 100 meters line of sight 

Warm Up Time 

About 1 minute 

PIR Detection Coverage 

Up to 12m x 110

°

  (at 2m mounting height & below 20

°

C) 

Frequency Range 

908.42 MHz (US) / 868.42 MHz (EU) 

*Specifications are subject to change without notice 

A501110874R 

 

                               

 

 

Federal Communication Commission Interference Statement 

This equipment has been tested and found to comply with the limits for a Class B 
digital device, pursuant to Part 15 of the FCC Rules.    These limits are designed to 
provide reasonable protection against harmful interference in a residential 

Содержание SP103

Страница 1: ...he tamper switch on the detector to complete the inclusion exclusion process FIGURE 1 Choosing A Mounting Location The recommended position for a PIR Detector is in the corner of a room mounted 2m from the floor At this height the detector will detect movement up to 6 12m depending on adjustment FIGURE 2a Also in this position the 110 degrees fan shaped detection pattern can normally offer greater...

Страница 2: ...he Detector will turn OFF the load or the lamp plugged into the On Off Module AN135 Lamp Module AD130 The red indicator LED on the load or the connected lamp will be off too 2 When the tamper switch is pressed the unit will enter normal mode Upon motion being sensed the Detector will turn ON the load or the lamp plugged into the On Off Module AN135 Lamp Module AD130 After the elapse of preset time...

Страница 3: ...is one minute For instance please always enter 60 120 or 180 seconds etc all of which are equivalent to 1 2 and 3 minutes respectively The time interval of wakeup cannot be entered 59 61 119 121 179 or 181 seconds Troubleshooting Symptom Possible Cause Recommendation Cannot carry out inclusion and association 1 Run out of battery power 2 Check if reverse battery polarity 3 Check if the detector is...

Страница 4: ...t 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation FCC Caution Any changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate this equipment ...

Отзывы: