3
Configuration Parameter # 3.
This parameter can be configured with the value of 0 through 127, where 0 means
power saving being enabled and others mean power saving being disabled.
PS : As long as the batteries have been refitted, the Detector will enable the power
saving function automatically.
Configuring the Phase Level of ON Command
The Configuration parameter that can be used to adjust the phase level of ON
command is transmitted is Configuration Parameter # 1. This parameter can be
configured with the value of 0 through 127.
Value 0: Set Device OFF(0x00)
Value 1-99: Set Device On (1-99)
Value 100-127: Set Device On to the last phase (0xFF)
Note:
0xFF means the device will be on to the last phase before the device was
turned off.
Wakeup Command Class
SP103 will send a Wakeup Notification Command if it has been included into a
Z-Wave network. The prerequisite is the connected Z-Wave controller needs to emit
a node ID and wakeup time interval to the Detector.
The SP103 will wake up every 4 hours (default) and resend the Wakeup Notification
Command unless configured for another time interval. The SP103 will stay awake
for 10 seconds and then go back to sleep to conserve battery life.
The time interval between Wakeup Notification Commands can be adjusted if you
have a device in which that is supported. Refer to that device’s instructions. The
time interval of Wakeup Notification Commands is counted on the basis of minute
and minimum criterion is one minute. For instance, please always enter 60, 120,
or 180 seconds etc. all of which are equivalent to 1, 2 and 3 minutes respectively.
The time interval of wakeup cannot be entered 59, 61, 119, 121, 179 or 181
seconds.
Troubleshooting
Symptom Possible
Cause
Recommendation
Cannot carry out
inclusion and association
1. Run out of battery
power
2. Check if reverse
battery polarity
3. Check if the detector
is out of order
1. Replace a new
battery
2. Refit the battery with
correct polarity
3. Ensure the detector is
working properly
Cannot control the
connected modules
1. Run out of battery
power
2. Check if the detector
is out of order
1. Replace a new
battery
2. Ensure the detector is
working properly
The detector not working
1. Run out of battery
power
2. Check if the mounting
location is proper
3. Check if the detector
is mounted above a
radiator or heater
4. Check if the detector
is out of order
1. Replace a new
battery
2. Reposition
its
mounting location
3. Remove the source of
interference or
reposition its
mounting location
4. Ensure the detector is
working properly
Specifications
Battery
1.5V AAA size x 2
Range
Up to 100 meters line of sight
Warm Up Time
About 1 minute
PIR Detection Coverage
Up to 12m x 110
°
(at 2m mounting height & below 20
°
C)
Frequency Range
908.42 MHz (US) / 868.42 MHz (EU)
*Specifications are subject to change without notice
A501110874R
Federal Communication Commission Interference Statement
This equipment has been tested and found to comply with the limits for a Class B
digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential