ThermalRite Blast Chiller Easy Touch Screen Manual
79
Rev02132016
Parameter
Description
Reach
In
120V
Reach
In
230V
Roll In
FEX
maximum evaporator fan speed %
[num]
100
100
100
DOO
max open door time before door
alarm [sec]
60
60
60
FCE
condenser fan set point [°C/°F]
77
77
77
HYF
upper differential condenser fan
action [°C/°F]
9
9
9
MCT
max condenser temperature
[°C/°F]
131
131
131
DCN
dirty condenser threshold [°C/°F]
0
0
0
GAS
low refrigerant amount alert
threshold [°C/°F]
0
0
0
DCR
differential for restarting blast
chiller after high condenser
temperature [°C/°F]
50
50
50
RMT
stop time during high condenser
temperature [sec]
180
180
180
PMT
max high condenser event before
high temp. Alarm [num]
3
3
3
TPB
time threshold for high condenser
temp. Alarm [min]
30
30
30
DTE
defrost ending temp related to
evap. Probe [°C/°F]
41
41
41
DRP
dripping time after defrost [sec]
60
60
60
DTO
defrost timeout [min]
10
10
10
ITD
interval between two consecutive
defrosts [hours]
8
8
8
DCD
max on-time drain heater [min]
8
8
8
SDT
ice detecting sensitivity in smart
defrost mode [num]
0
0
0
SD1
first daily defrost [hour]
0
0
0
SD2
second daily defrost [hour]
0
0
0
SD3
third daily defrost [hour]
0
0
0
SD4
fourth daily defrost [hour]
0
0
0
SPX
door frame heater set point [°C/°F]
14
14
14
COS
average power factor of equipment
[num]
5
5
5
PR1
declared power connected to relay1
[num]
0
0
0
PR2
declared power connected to relay2
[num]
0
0
0
PR3
declared power connected to relay3
[num]
0
0
0
PR4
declared power connected to relay4
[num]
0
0
0
PR5
declared power connected to relay5
[num]
0
0
0
PR6
declared power connected to relay6
[num]
0
0
0
PR7
declared power connected to relay7
[num]
0
0
0