EverExceed Smart IT Cabin
Solution User Manual
2.2.2 Outside machine wiring diagram (
Figure
2-4)
Figure
2-4 wiring diagram(detail in CAD drawing)
2.2.3 Connecting Copper Pipes
1. General Principles
1) Use copper pipes with quick thread connector to connect the indoor unit
and the outdoor unit. If the pipe length exceeds the standard pipe length
and straight copper pipe is used, piping joints must be brazed.
2) Follow standard industry procedures in selection and placement of pipe,
system evacuation and charging with refrigerant (only when pipeline is
too long).
3) Give considerations to pipeline pressure drop, oil return to the
compressor, to avoid oil leakage and clogging in parts of the system and
minimize noise and vibration to the greatest extend.
2. Installation notes of connector
The connectors of the unit are located on the AC indoor unit and outdoor unit
and on top of the cabinet. Be careful when connecting the quick thread
connector. Read through the following steps before making connection.
1) Remove the dust-proof caps.
2) Carefully wipe coupling seats and threaded surface with a clean cloth.
8
/
32
www.everexceed.com