Instruction manual for SPECLINE PRO 700 series power supply units
19
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-01-18 03:29
TECHNICAL PARAMETERS
PARAMETERS \ TYPE
SPECLINE PRO 700
Part number
W/SPPRTO-000K70/00
Rated output power (Apparent / Active)
1)
350 VA / 200 W
The maximum output power of 30 s (Apparent /
Active)
700 VA / 400 W
GENERAL DATA AND ENVIRONMENTAL
Topology
VFD (offline)
Number of phases (in/out)
1 / 1
Housing Type
Tower
Operating temperature
2)
0 ÷ +40 °C
Storage temperature
0 ÷ +45 °C
Relative humidity during operation
20 ÷ 80 % (non-condensing)
Relative humidity during storage
20 ÷ 95 % (non-condensing)
Operating elevation
3)
< 1000 m
Protection level
IP20
Environment of installation
Technical rooms / industrial rooms with low level of pollution
Cooling
Gravity
INPUT
Rated input voltage
230 V AC
Input voltage range and tolerance
~ 184 ÷ 264 V ± 2 %
Input voltage rated frequency
50 Hz
Input voltage frequency range and tolerance
45 ÷ 55 Hz ± 1 Hz
Transfer thresholds: Mains – UPS
~ 184 ÷ 264 V ± 2 %
OUTPUT
Rated output voltage
230 V AC
Output voltage range and tolerance - normal
mode
~ 184 ÷ 264 V ± 2 %
Output voltage range and tolerance - battery
mode
~230 V ± 5 %
Shape of output voltage (battery mode /
normal mode)
Sine wave / same as input
Output voltage rated frequency
50 Hz
Output frequency range and tolerance - mains
operation mode
Synchronously
Output frequency range and tolerance - battery
mode
50 Hz ± 1Hz
Output voltage filtering
LC, RFI/EMI filter, varistor TVSS
Transfer thresholds: UPS– Mains
~ 189 V / 259 V ± 2 %
Transfer time to battery mode
< 3 ms
Transfer time to normal mode
0 ms
BATTERIES AND TYPICAL RUNTIME
Internal Batteries
12 V / 7 Ah VRLA
Number of internal batteries
2
Maximum overall internal batteries capacity
14 Ah
External Batteries
6 x 12 V / 7 Ah VRLA
Maximum number of EBMs 42 Ah
3
Backup time - internal batteries
( 100 % / 50 % Pzn)
24 / 55 min
Backup time - internal bat 1 EBM
( 100 % / 50 % Pzn)
120 / 290 min
Backup time - internal bat 2 EBM
( 100 % / 50 % Pzn)
250 / 560 min
Backup time - internal bat 3 EBM
( 100 % / 50 % Pzn)
370 / 800 min
Rated voltage DC circuit
12 V DC
EBM (42 Ah) Maximum charging time - after
discharging at 80 % Pmax
*
10 h