Instruction manual for SPECLINE PRO 700 series power supply units
17
www.ever.eu
Technical Service, tel.: +48 61 6500 400
2016-01-18 03:29
COMMENTS REGARDING OPERATION
WARNING!
EVER SPECLINE PRO 700 power supply units are C2
category appliances. In residential environments, the product may
interfere with radio signals, which may require additional precautions to
be employed by the user.
FUSE REPLACEMENT
In the event of the connection of a device with a power consumption level that
considerably exceeds the nominal value, or a short circuit in the mains socket, the
fuses may burn out (the fuses are located in a holder
– cf. connection panel). In order
to replace a fuse, turn the unit off with the switch, disconnect mains power (e.g. at the
building’s switchboard), remove the fuse holder, and install a new fuse with
parameters that are concordant with the specification of the power supply unit. The
set contains one spare mains fuse and one spare battery fuse.
INTERACTION WITH ELECTRICAL GENERATORS
EVER SPECLINE PRO 700 power supply units are VFD-class devices that
synchronise themselves with the mains voltage. The unit has been designed to
tolerate voltage fluctuations in the range of 184-264 V and changes in the frequency
of ±5 Hz in relation to the model frequency of 50 Hz. The generator frequency value
may be variable over time and depends on changes in the load values. If the
generator voltage frequency changes were to exceed this tolerance, the power
supply unit may consider such a frequency value as incorrect and switch to battery
operation.
OUTPUTS
The connectors used in the power supply unit have a maximum current of 40 A.
STORAGE, MAINTENANCE, AND TRANSPORT
The power supply unit should be stored in a cool and dry place, and in its working
position. It is recommended to store battery modules with fully charged batteries:
at a temperature between 0°C ÷ +30°C, the battery should be charged every 6
months;
Содержание SPECLINE PRO 700
Страница 1: ......