EVCO S.p.A.
Vcolor 818
| Installer manual ver. 1.1 | Code 144VC818E114
page 24 of 94
6.3
Temperature-controlled hard blast chilling and storage
The temperature-controlled hard blast chilling and storage cycle is divided into the following three phases:
-
blast chilling hard phase
-
blast chilling
-
storage.
On conclusion of a phase, the device passes automatically to the next.
Operate as indicated to start the cycle:
1.
Make sure the device is in the "on" status.
2.
Make sure that the keyboard is not locked and that no procedure is in progress.
3.
Press and release the key (1), press and release the key (2) and then press and release the key (3) and finally
press and release the key (4): the device will display the blast chilling end temperature and the work set-point
during blast chilling.
4.1
Press and release the MENU key and then press and release the key (4) or the key (5) to select the blast
chilling end temperature and the work set-point during blast chilling.
4.2
Press and release the key + (6) or the key – (7) to modify these values and then the ESCAPE key to memorise
them; these values can also be memorised through parameters r3 and r7.