EVRS 200 range

Controllers in split execution for refrigerated display cases, ice-cream and sweet counters and plug ins.

EN

ENGLISH

DIMENSIONS AND INSTALLATION
User interface dimensions and installation

The dimensions are expressed in mm (in); panel installation is envisioned, with elastic retainer wings (det. A).
For the dimensions and installation of the control module, see page 8.

To facilitate removal f the user interface, slightly smooth the internal longitudinal edges of the drilling template before
installation (det. B and C).

ELECTRIC CONNECTION
Electric connection

drilling templ ate

IMPORTANT

Read this document thoroughly before installation and
before use of the device and follow all recommendations;
keep this document with the device for future consulta-
tion.
Only use the device in the way described in this document;
do not use the same as a safety device.

The device must be disposed of in compliance with
local Standards regarding the collection of electric
and electronic equipment.

1

DIMENSIONS AND INSTALLATION

1.1

Installation warnings

-

the thickness of the panel on which the user interface is
to be installed must be between 0.8 and
2.0 mm (0.031 and 0.078 in)

-

make sure that the device work conditions (temperature
of use, humidity, etc.) lie within the limits indicated;
see chapter 13

-

do not install the device near to any heat sources (heating
elements, hot air ducts etc.), equipment containing
powerful magnets (large diffusers, etc.), areas affected
by direct sunlight, rain, humidity, excessive dust, me-
chanical vibrations or shocks.

-

any metal parts in proximity of the control module must
be at a distance such that they do not compromise the
safety distances.

-

in compliance with Safety Standards, the device must
be installed correctly and in a way to protect against
any contact with electric parts; all parts that ensure
protection must be fixed in a way that they cannot be
removed without the use of tools.

2

ELECTRIC CONNECTION

2.1

Warnings for the electric connection

-

do not use electric or pneumatic screwdrivers on the
device terminal board

-

if the device has been taken from a cold to hot place,
humidity could condense inside; wait about 1 hour
before powering it

-

make sure that the power supply voltage, the frequency
and the operational electric power of the device,
correspond with those of the local power supply; see
chapter 13

-

disconnect the device power supply before proceeding
with any type of maintenance

-

position the power cables as far away as possible from
the signal cables

-

for repairs and information regarding the device, contact
the EVCO sales network.

3

USER INTERFACE

3.1

Preliminary notes

Operating Statuses:
-

“on” state (the device is powered and is on: the regulators
can be switched on)

-

“stand-by” status (the device is powered but is
switched off via software: the regulators are switched
off; the possibility to manually switch on/switch off
the cell light or auxiliary output depends on param-
eter u2)

-

the “off” status (the device is not powered).

Hereafter, with the word “start-up” means the passage
from “stand-by” status to “on” status; the word “shut-
down” means the passage from “on” status to “stand-by”
status.
When the power is switched back on, the device dis-
plays the status that it was in at the time it was discon-
nected.

3.2

Device switch-on/off in manual mode

Operating Statuses:
1.

Make sure that the keyboard is not locked and that no
procedure is in progress.

2.

Hold the key down for 2 s: the LED will switch off/on.

Using the digital inputs it is also possible to remotely switch
on/off the device.

3.3

The display

If the device is switched on, during normal operation, the
display will show the cell temperature, except during
defrosting, when the device will show the temperature
established with parameter d6.
If the device is switched off, the display will be switched
off.

Cabi

net

Evap. Fan

D

e

frosting

Cabi

ne

t l

ig

ht

(confi

g

.)

Al

ar

m

(confi

g

.)

E

qui

pm

ent

earth

Not available

In the EVRS205 model

D

oor m

ic

ro s

w

itc

h

/m

inut

es

 f.

 1

D

oor m

ic

ro s

w

itc

h

/m

inut

es

 f.

 2

User interface

Cabi

net

D

oor m

ic

ro s

w

itc

h

/m

inut

es

 f.

2

Third Input

Control module

TTI MODBUS port

Phase

Power supply neutral

Earth

Содержание EVRS 200 Series

Страница 1: ...ELECTRIC CONNECTION 2 1 Warnings for the electric connection do not use electric or pneumatic screwdrivers on the device terminal board if the device has been taken from a cold to hot place humidity...

Страница 2: ...on of compressor operation hours changing the working setpoint with the procedure described in 9 1 The operations cause the display of the label Loc per 1 sec To unlock the keyboard 1 Hold the key and...

Страница 3: ...e the or key within 15 s to set 149 5 Press and release the key or do not operate for 15 sec 6 Hold the and keys down for 4 s the display will show dEF 7 Press and release the key 8 Press and release...

Страница 4: ...e COH will not be activated the compressor blocked alarm CSd code will never be activated the alarm output will be activated provided that parameter u1 and or parameter u11 is set at 3 the condenser f...

Страница 5: ...3 3 compressor 2 switch on delay from compressor 1 switch on only if u1 and or u11 7 10 PARAM MIN MAX U M EVRS204 EVRS205 DEFROSTING d0 0 99 h 8 8 if d8 0 1 or 2 defrosting interval 11 0 interval def...

Страница 6: ...evaporator fan will remain switched off F4 0 240 s 60 60 time duration that evaporator fan is switched off during operation for a low percentage of relative humidity when the compressor is switched of...

Страница 7: ...er fan will be switched on the display will show the flashing code iA and the buzzer will be activated until the input is deactivated when the input has been activated the number of times established...

Страница 8: ...will function as if parameter d8 were set at 0 14 if when defrosting is activated the operating dura tion of the compressor is less than the time estab lished with parameter d5 the compressor will re...

Отзывы: