EVCO S.p.A.
c-pro 3 giga | Hardware manual ver. 3.0 | Code 144CP3GI304
page 32 of 44
9.4
Configuration parameters of the “UART1” sub-menu of the “Networks” menu
The parameters are only visible if the application software is set up for the RS-485 (MODBUS MASTER/SLAVE, BACnet MS/TP) port to be configured to support the
MODBUS communication protocol.
PARAMETER
MIN.
MAX.
U.M.
DEF.
DESCRIPTION
Address
1
247
- - -
1
device MODBUS address (important only if the communication protocol
is MODBUS slave)
Baud rate
- - -
- - -
- - -
9600
baud rate of the MODBUS communication
1200
=
1,200 baud
2400
=
2,400 baud
4800
=
4,800 baud
9600
=
9,600 baud
19200
=
19,200 baud
28800
=
28,800 baud
38400
=
38,400 baud
57600
=
57,600 baud
Parity
- - -
- - -
- - -
EVEN
parity of the MODBUS communication
NONE
=
none
ODD
=
odd
EVEN
=
even
Stop
- - -
- - -
- - -
1 BIT
number of stop bit of the MODBUS communication
1 BIT
=
1 bit
2 BIT
=
2 bit
Timeout
2
240
s
10
timeout of the local MODBUS communication, that is of the device (when
the time set by this parameter from the sending of the request has
elapsed without receiving an answer, the sending of the request is con-
sidered to have failed and the next request is sent; this is important
only when the communication protocol is MODBUS master)
9.5
Configuration parameters of the “UART2” sub-menu of the “Networks” menu
The parameters are only visible if the application software is set up for the RS-485 MODBUS slave port to be configured to support the MODBUS communication proto-
col.
PARAM.
MIN.
MAX.
U.M.
DEF.
DESCRIPTION
Address
1
247
- - -
1
device MODBUS address (important only if the communication protocol
is MODBUS slave)
Baud rate
- - -
- - -
- - -
9600
baud rate of the MODBUS communication
1200
=
1,200 baud
2400
=
2,400 baud
4800
=
4,800 baud
9600
=
9,600 baud
19200
=
19,200 baud
28800
=
28,800 baud
38400
=
38,400 baud
57600
=
57,600 baud
Parity
- - -
- - -
- - -
EVEN
parity of the MODBUS communication
NONE
=
none
ODD
=
odd
EVEN
=
even
Stop
- - -
- - -
- - -
1 BIT
number of stop bit of the MODBUS communication
1 BIT
=
1 bit
2 BIT
=
2 bit
Timeout
0
9999
ms
1000
timeout of the local MODBUS communication, that is of the device (when
the time set by this parameter from the sending of the request has
elapsed without receiving an answer, the sending of the request is con-
sidered to have failed and the next request is sent; this is important
only when the communication protocol is MODBUS master)