6
CONFIGURATION
6.1
Initial information
To configure the device, users will need a programmable controller with a built-in or remote user interface.
6.2
Example of configuration using the remote EPJgraph user interface
1.
Make sure neither the device nor the remote user interface is powered up.
2.
Connect the device and the remote user interface as shown in the diagram below without powering up the device.
3.
Power up the device.
4.
Use the remote user interface as shown in the following procedures.
5.
Touch the LEFT and ENTER keys for 2 s: the dis-
play will show the “Network Status (CAN)”
screen.
6.
Touch the ENTER key: the display will show the
main menu.
7.
Touch the UP or DOWN key to select the “Net-
works” menu.
8.
Touch the ENTER key.
9.
Touch the UP or DOWN key to select the “CAN
BUS” sub-menu.
10.
Touch the ENTER key to access the menu: the
display will show the "Input Password” screen.
11.
Touch the ENTER key again.
12.
Touch the UP or DOWN key to set “
-19
”.
13.
Touch the ENTER key: the display will show the
“CAN Network” screen.
14.
Touch the UP or DOWN key to select “Network
Node”.
15.
Touch the ENTER key.
16.
Touch the UP or DOWN key to set the device
node (for example “[1]”).
17.
Touch the ENTER key.
18.
Touch the DOWN key.
19.
Touch the ENTER key.
20.
Touch the UP or DOWN key to set the address of
the device node (default “1”).
21.
Touch the ON/STAND-BY key a few times to re-
turn to the previous displays.
22.
Disconnect the device from the mains.
23.
Power up the device.