EVCO S.p.A.
EVDRIVE04 | User manual ver. 1.1 | Code 144EPD4I114
Page 50 of 78
1 = barA
P2YM
1660
RW
P2Ym
300.00 barG/barA
1.00
Manufact.
Y max value
P2Ym 1661
RW
-
300.00
P2YM
barG/barA
0.00
Manufact.
Y min value
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menu
Probe settings: analog input AI3
Piu3
1662
RW
3
3
- - - -
3
Manufact.
analog input AI3 function
3 = suction temperature probe
Pia3
1663
RW
1
6
- - - -
1
Manufact.
analog input AI3 probe type
1 = NTC probe
6 = Pt 1000 probe
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menu
Probe settings: analog input AI4
Piu4
1670
RW
4
4
- - - -
4
Manufact.
analog input AI4 function
4 = suction pressure probe
Pia4
1671
RW
10
30
- - - -
20
Installer
analog input AI4 probe type
10 = 4÷20 mA transducer
(0÷10 Barg)
11 = 4÷20 mA transducer
(0÷16 Barg)
12 = 4÷20 mA transducer
(0÷30 Barg)
13 = 4÷20 mA transducer
(0÷50 Barg)
20 = 0÷5 V ratiometric transducer
(0÷7 Barg)
21 = 0÷5 V ratiometric transducer
(0÷25 Barg)
22 = 0÷5 V ratiometric transducer
(0÷60 Barg)
30 = scaling
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menu
Probe settings: analog input AI4
scaling
P4Xty 1672
RW
0
3
- - - -
2
Manufact.
X type
0 = 0-20 mA
1 = 4-20 mA
2 = 0-5 V
3 = 0-10 V
P4XM
1673
RW
P4Xm
0:20.00
1:20.00
2:5.00
3:10.00
- - - -
5.00
Manufact.
X max value