Evacuator Evacuator Synergy RF Скачать руководство пользователя страница 3

 

www.evacuatoralarms.com 

Note: Each system must have one Master Device (00), to obtain maximum performance we 
recommend the master is in the centre of the site. In order to identify the Device numbers we 
recommend using the Device number box located on the side of the stickers. 

Fitting the Antenna  

The rubber duck antenna should now be fitted to the Silver BNC docking point located on the top of 
the front cover. The Antenna should be placed over the BNC connector and twisted in clockwise 
motion until it locates into place. Test that it has been located correctly by gently pulling on the 
Antenna in an outwards motion. 

Connecting the Battery and Fitting Front cover 

The battery should be secured onto the back plate with the industrial Velcro supplied. Also be sure 
that the black and red power leads are orientated to the right hand side of the moulding back plate 
facing up. Now connect the white (male) two way plug from the battery into the white (female) plug 
located on the inside of the front cover. 

Once connected offer the front cover upto the wall mounted back plate making sure that the battery 
lead does not foul on the central screw boss of the back plate. Once connected you will notice that 
the LED on the front panel begins to flash. 

When the front cover is located onto the back plate replace the M4 screw into the bottom of the 
Siren Flasher/Strobe hole and locate it into the threaded insert in the back plate. This can now be 
tightened down to pull the front cover flush to the back plate. DO NOT OVERTIGHTEN OR USE A 
BATTERY OPERATED DRILL/SCREWDRIVER TO TIGHTEN THE SCREW AS THIS WILL RESUKT IN 
PERMENANT DAMAGE TO THE FLASHER SOUNDER UNIT. 

Status LED 

LED 

Status 

Red & Green alternate flashing  

Power Up Sequence 

Green Flashing (30 sec interval) 

Standby  

Blue Flashing (30 sec interval) 

Standby Master Device (Set 00) 

Red Blinking 

Low Battery 

Blue Solid 

Test Mode 

Red Solid 

Reset Mode 

White Flashing 

Alarm Mode 

Green Rapid Flashing 

Out of Range 

Red Rapid Flashing 

Out of Range & Low Battery 

 

Testing the System 

Testing the system is easy. If you are using the system without a Base Station you will need to 
purchase an Evacuator Secure Key Fob. To put the system in to Test swipe the fob over the Test 
System Logo on the left hand side of the product on any device in the system. This will then turn the 
Status LED Solid Blue on all of the linked Devices. You will then have to walk the site making sure all 
LED's are blue. When you are happy all LED's are blue in the system you can swipe the Key Fob over 