Evacuator Evacuator Synergy RF Скачать руководство пользователя страница 2

 

www.evacuatoralarms.com 

unlimited

 number of Sounder /Strobe units subject to System design criteria. These units will be 

described as 

“Drones 

“in this instruction manual.

 

Master Unit (00) 

Each system must have its Master unit set first, this is done by setting Dial 2 to 0 and Dial 3 to 0. Your 
system can only have one Master Unit. To get maximum performance from your system you are best 
locate your master unit at the centre of the site. The master can either be a Call Point, Auto Detector 
or Sounder/Strobe. 

Slave Units (1-39) 

Slave units can be either a Call Point, Sounder/Strobe, Auto Detector or Base Station. When 
numbering these devices we recommend numbering them in numerical order for testing.  

Drones (40) 

Only the Sounder/Strobe unit can be set as a drone unit. This is done by setting dial 2 to 4 and dial 3 
to 0 making it device 40. We recommend a maximum of 2 per Slave unit in your system i.e. 20 slaves 
and 40 Drones. 

 

 

 

 

 

 

As you can see above there are 3 dials, dial 1 on the left is 

NOT 

needed for device numbering. Dial 2 

and 3 are used for your device numbering, as you can see dial 2 is set to 0 and dial 3 to number 3. 
This makes the device number 03. to set a device to number 20 for example dial 2 would be set to 2 
and dial 3 set to 0. 

Note: When setting the dials, please use the setting driver supplied 

Zone Dial (Dial 1) 

This dial is factory set to "0" and will not need to be changed unless you wish to separate a number 
of systems that will be operating within 2km of each other. This will be used for example if there are 
several contractors using the system on the same site or in the same area. It may also be beneficial 
to separate zones for floors on larger projects.   

Device Dials (Dial 2 and 3) 

These dials are used to number the Devices as above. Dial 2 will only be used from 0-4, Dial 3 will use 
0-9. 

Отзывы: