54
Product-manual Model: 637+/D6R KD6R
07-02-09-01-E-V0402.doc
6 Wiring
instructions
6.1
General Information
Digital servo drives are designed for
operation in metallic grounded enclosures
.
For perfect operation as well as for observance of all regulations the
front board must be
connected with the enclosure electrically and fixed.
6.2
Control cabling
Recommended cross section 0,25 mm².The control signal lines must be laid seperate from the
power signal lines.(see chapter 6.7.1)
The resolver cable should contain three shielded pairs
and
be shielded as a whole. The shielding
should be connected to the ground spread out on the regulator side.We recommend using
Eurotherm resolver cable
KIR.
Cable for transmitting data are always to be laid shielded !
6.3
Power cabling
Recommended section according to rated current. Use only 75° Cu-cables.
6.4
Installation of the rack
When the rack is secured not in a hinged bay but on a mounting plate, it is recommended to do the
wiring of the connections for the power connector X50 on the rear of the rack before installing.
With hinged-bay installation, the customer must ensure that the parts sensitive to voltage such as
the Ucc bus, mains supply lines, etc., are protected against electric shock.
6.5
Analog setpoint
The setpoint input is a differential input. Therefore the poling can be done depending on the
requirements.
Important: the setpoint voltage must be galvanically connected to the reference potential of the
control connections (plug X10). It is possible to connect one pole directly to GND.
6.6
Safety rules
CAUTION !
Plug / unplug all modules only when
Ucc (DC-BUS) is off, that is, the green LED on the power supply module is off and the
discharge time > 3 minutes has elapsed.
The user must ensure protection against accidental touching.
6.7
Electromagnetic compatibility (EMC)
Confirmity in accordance with the EEC Directive 89/336/EEC has been evaluated using a
reference-system, consisting of a compact type drive and a line-filter on mounting-plate,
connected to an AC-syncronous motor.
Mainly responsible for EMC-emissions is the motor cable. So this has to be installed exeptional
carefully.
The layout of grounding is very important. Grounding has to be low-impedant for high frequences.
That means, all ground-connecting parts have to use area.
The measurements made are valid under the use of Eurotherm - cables, suppression aids and line
filters and by application of the following wiring instructions:
Содержание 637+/D6R KD6R
Страница 78: ...78 Product manual Model 637 D6R KD6R 07 02 09 01 E V0402 doc Certificates ...
Страница 79: ...Product manual Model 637 D6R KD6R 07 02 09 01 E V0402 doc 79 Certificates ...
Страница 80: ...80 Product manual Model 637 D6R KD6R 07 02 09 01 E V0402 doc Certificates ...
Страница 81: ...Product manual Model 637 D6R KD6R 07 02 09 01 E V0402 doc 81 Certificates ...
Страница 82: ...82 Product manual Model 637 D6R KD6R 07 02 09 01 E V0402 doc Certificates ...
Страница 83: ...Product manual Model 637 D6R KD6R 07 02 09 01 E V0402 doc 83 Certificates ...
Страница 85: ...Product manual Model 637 D6R KD6R 07 02 09 01 E V0402 doc 85 16 Notes ...