2408
i Indicator Engineering Manual
4.6.5
Module 1, 2 and 3 Configuration Lists
The identity of a module fitted in slots 1, 2 or 3 is shown by the first parameter in the module lists.
•
If the module is a single output only channel
<
A
>
is shown
•
If the module is a dual output channel
<
a
>
and channel
<
C
>
are shown
•
If the module is a triple output Channel
<
A
>
, channel
<
b
>
and channel
<
C
>
are shown
Module configuration lists are summarised below:-
MODULE 1
MODULE 2
MODULE 3
LIST HEADINGS:
1a
,
1b
,
1C
2a
,
2b
,
2C
3a
,
3b
,
3C
(Note: The list heading corresponds to the
terminal number to which the input/output is
wired)
Note: Channel ‘
b
’ only appears if a dual or triple channel module is fitted. Channel ‘
C
’ only appears if a triple channel
module is fitted
Customer setting in each channel number
Module
Parameters
Option
Meaning
1A
1B
1C
2A
2B
2C
3A
3b
3C
id
Identity
of
module
nonE
Module not fitted
rELY
Relay output
LoG
Logic output
LoG.i
Logic or contact closure input
dC.iP
2
nd
analogue input module
(Module 3 only)
dc.re
DC retransmission
TPSU
Transmitter power supply
SG.SU
Strain gauge power supply
4.6.6
Changeover Relay
or
Dual Relay Output Module
4.6.7
Triple Logic Output Module
The parameter lists are the same for each of these modules as listed below:-
id
Identity of
module
reLY
Relay
Customer settings in each channel
LoG
Logic
1A 1B 1C 2A 2B 2C 3A 3b 3C
Func
Function of
output
nonE
diG
Module operation
turned off
Digital
SenS
Sense of the
output
nor
inv
Output energises when
TRUE
Output de-energises
when TRUE (default for
alarms)
If
Func
=
nonE
no further parameters are shown
1---
Alarm 1
YES
/
no
2---
Alarm 2
YES
/
no
3---
Alarm 3
YES
/
no
Alarms are
4---
Alarm 4
YES
/
no
attached to the
Sbr
Sensor break
alarm
YES
/
no
output in the
same
Span
Span
YES
/
no
way as relay
rmt.F
Remote failure
YES
/
no
output 1
iP1.F
Input 1 fail
YES
/
no
nw.AL
New alarm
YES
/
no
The changeover relay output module has a single output so the above parameters are shown under list <
-A
> only
The triple logic module has three outputs so the above parameters are shown under lists
’
<
-A
>, <
-b
>, and
’
<
-C
>
The dual relay module has two outputs so the above parameters are shown under lists
’
<
-A
> and <
-C
>
1A
3C
to
Part Number HA027240 Issue 5.0 Feb 2015