Example: To Configure Alarm 2 to Operate When Input 2 Exceeds A Set Value
Do This
This Is The Display You Should See
Additional Notes
Enter configuration level as described in section 4.2.1.
The next two parameters – Alarm Latching and Alarm Blocking may be set in the same way if they are required.
4.5.4
Alarm Inhibit
The alarm inhibit feature may be used to prevent any alarms from being indicated until a ‘noisy’ process variable
has settled. Alarm inhibit is activated by a digital input on either Digital Input 1 or 2 - see section 4.5.4. When the
digital input is turned to OFF any alarms which are active will be displayed. If a delay has been set on the alarm,
the delay period will start from the time when the input is turned OFF. Entering Alarm Inhibit resets both the
alarm delay timer and latched alarms.
The action of Alarm Inhibit is shown in the diagram below for a Full Scale High Alarm.
Figure 4-4: Effect of Alarm Inhibit
FH2
AL 2
2 secs
1.
Press
until the
‘Alarm List’
header is shown
2.
Press
until
<
AL 2
>
is
shown
3.
Press
or
until
<
FH2
>
is
shown
The display will return to
<
AL 2
>
after
approximately 2 seconds
<
FH2
>
is Full Scale High alarm on
input 2
AL
With Alarm I
Delay
PV
No Alarm Inhibit
With Alarm
Inhibit
High Alarm setpoint
threshold
Alarm Inhibit
input ON
Alarm Inhibit
input OFF
Delay time
Alarm indicated
Alarm indicated
Alarm indicated
Time
PV
High Alarm State
Alarm Inhibit Input
PV
42
Part Number HA027240 Issue 5.0 Feb 2015