Engineering Manual 2408
i Indicator
4
CONFIGURATION LEVEL
The 2408
i
indicator is supplied configured in accordance with the ordering code (see section 5). The
configuration of the indicator, as defined by columns 11 to 16 of the order code, can be changed on site, if
necessary, to meet the requirements of the installation. Similarly, the positions or types of plug in module can be
changed if required. This section describes the procedures to be followed.
4.1
Hardware configuration - I/O Modules
Figure 4-1: View of the Plug-in Modules
Optional plug-in modules are fitted simply by sliding them into the
relevant position as shown in Figure 4-1. The connections for these
modules are made to the upper row of connector blocks as shown in
section 1.3.
When a module is added, removed or changed the indicator will flash
hardware error ‘<HWEr> on power up. To acknowledge this it is
necessary to go into configuration level.
1.
Press either
or
until <ConF> is displayed.
2.
Press
or
to enter the configuration level password
passcode (factory default 2)
3.
Press either
or
again and the hardware error is
acknowledged
The full list of modules available is shown in the ordering code.
34
Part Number HA027240 Issue 5.0 Feb 2015