![Eurotherm Chessell 4100G Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/eurotherm-chessell/4100g/4100g_technical-manual_2440593033.webp)
100mm GRAPHICS RECORDER TECHNICAL MANUAL
HA249875
Issue 1 Jan 99
Section 2
Page 2 - 12
2.4 RECORDER MESSAGES (Cont.)
EEPROM DB DEFAULTED
This message appears at power up if any part of the database is found to be corrupt at power-up, and the database has
been defaulted.
INPUT CHAN FAILURE
Input channel hardware fault, or if configured to use a remote CJ, the remote CJ is disabled or is not providing a suit-
able signal.
INVALID INDEX
This message appears if a channel / totaliser etc. number is entered which is greater than the maximum number of
channels / totalisers etc. fitted.
INVALID CONFIG
This message appears if one part of the configuration conflicts with another e.g. if the linearisation type does not
match the input type.
MODEM FAILURE
Occurs if:
a. Modem not fitted/powered-on
b. Wiring to Modem incorrect
c. Incompatible type of Modem in use
d. User-entered initialisation string not recognised.
OUTPUT CH FAILURE
Output channel hardware fault
> RANGE
This appears whenever the value of the I/O signal lies above the currently selected hardware range.
< RANGE
This appears whenever the value of the I/O signal lies below the currently selected hardware range.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание 4100G
Страница 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 53: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 55: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 57: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 61: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...