100mm GRAPHICS RECORDER TECHNICAL MANUAL
HA249875
Issue 1 Jan 99
Section 2
Page 2 - 6
Conf:Serial Comms
Conf:Alarm Messages
Conf:System error
Conf:Disk
Conf:Event 1
Conf:Transfer
Conf:Access
Conf:Adjust
Conf:Adjust
1
2
Channel : Range
Low point is 0.00
Low Point is 0.00
.
2
3
4
5
6
7
8
9
1
0
+/-
Use keyboard to enter what the Channel
values should be, then press Enter.
Adjust input
Adjust input
Apply to Ch 1..1
Remove from Ch 1..1
View Adjust Ch 1..1
1
3
4
5
Low Point Ready
Ch 1 1.203
Low Point Ready
Ch1 field shows current value of channel 1.
Selecting this area allows other channels'
values to be viewed.
Operate 'Enter' when all readings stable.
High Point Ready
Ch 1 99.87
High Point Ready
Ch1 field shows current value of channel 1.
Selecting this area allows other channels'
values to be viewed.
Operate 'Enter' when all readings stable.
Channel : Range
High point is 99.87
High Point is 100.00.
.
2
3
4
5
6
7
8
9
1
0
+/-
Use keyboard to enter what the Channel
values should be, then press Enter.
After a few seconds, 'Adjustment complete'
appears in status line.
2
!
i n s t r u m e n t
1 5 : 0 6 : 0 9
0 6 / 1 2 / 9 6
!
i n s t r u m e n t
1 5 : 0 6 : 1 4
0 6 / 1 2 / 9 6
!
i n s t r u m e n t
!
1 5 : 2 0 : 3 7
0 6 / 1 2 / 9 6
!
i n s t r u m e n t
1 5 : 2 1 : 4 5
0 6 / 1 2 / 9 6
!
i n s t r u m e n t
1 5 : 4 4 : 0 0
0 6 / 1 2 / 9 6
!
i n s t r u m e n t
1 4 : 4 5 : 3 7
0 6 / 1 2 / 9 6
Apply to Ch 1..
2
1 5 : 0 6 : 3 0
0 6 / 1 2 / 9 6
1
2
3
i n s t r u m e n t
2.2 INPUT ADJUST
2.2.1 Adjustment procedure
This feature allows input channels to be adjusted to make allowance for non-standard inputs. The technique used is to
apply a known input at the low end of the input range for each channel in question. Once the reading displayed by the
recorder has stabilised, the 'correct' value is entered. The process is repeated for a value near the high end of the in-
put range.
Figure 2.2.1a Input adjust configuration pages
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание 4100G
Страница 3: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 53: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 55: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 57: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 61: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...