Blower operates continuously 

Time interval between blow-throughs (setting No. 6) set at 0 

 adjust the value. 

Boiler is overheating 

The blow-through time setting (5) is too long or the time interval between blow-throughs is too 
short (setting No. 6) 

 adjust the value. 

The blower power too high 

 adjust the preset values of the power of the blower (3) and (4); 

throttle back the blower. 

Controller emits a buzzing sound 

Loose coils in the interference filter 

 does not impact the correct operation of the device. 

Controller knob operates erratically 

Pulse generator damage 

 send the device to the service. 

15.

 

STANDARDS AND CERTIFICATES 

EUROSTER 11W

controller conforms to the following EU Directives: EMC, LVD and RoHS. 

The EC Declaration of Conformity is published and available at:

 

http://www.euroster.com.pl

 

16.

 

TECHNICAL DATA

 

Controlled device 

CH pump and blower

 

Supply voltage 

230 V 50 Hz

 

Maximum pump output load 

2 A 230 V 50 Hz

 

Maximum blower output load 

0.5 A 230 V 50 Hz

 

Maximum power consumption 

1.6 W

 

Temperature measurement range 

from -5 

°C to +110

 

°C

 

CH temperature adjustment range 

from +20 

°C to +80

 

°C

 

Boiler temperature adjustment range 

from +40 

°C to +80

 

°C

 

Temperature adjustment accuracy 

°C

 

Hysteresis range 

from 2 

°C to 10

 

°C

 

Visual signalization 

backlit LCD

 

Operation temperature 

from +5 

°C to +40

 

°C 

 

Storage temperature 

from 0 

°C to +65

 

°C

 

Ingress protection rating 

IP40

 

Color 

black

 

Mounting method 

wall-mounted, screw anchors

 

Weight of the controller with cables 

0.70 kg

 

Length of cables 

1.5 m 

 

Standards, approvals, certificates 

Conformity to EMC, LVD and RoHS

 

Warranty period 

2 years

 

Dimensions (width / height / depth) mm 

150 / 90 / 52

 

It is recommended to use fans equipped with a reactive power compensation circuit. 

Feeding  the  controller  (also  in  the  emergency  mode)  with  a  non-sinusoidal  voltage 
may result in increased energy losses in the pumps and in the fan, and contribute to 
malfunction of the whole system.

 

17.

 

KIT CONTENTS 

a)

 

controller with 1 temperature sensor 

b)

 

sensor hose clip 

c)

 

screw anchors 

d)

 

manual 

e)

 

mounting template 

Содержание 11W

Страница 1: ...urnace and controls the operation of the CH circulation pump EUROSTER 11W controller is equipped with an ANTI STOP function that prevents seizing of an idle pump rotor It automatically turns the pump...

Страница 2: ...n the boiler in a point specially designed for that purpose or on an unshielded outlet pipe of the CH boiler as close to the boiler as possible using hose clip tighten the sensor to the pipe and cover...

Страница 3: ...ter displayed while previewing or changing the setting 2 Boiler temperature sensor icon 3 Manual operation mode icon lit while the temperature is manually adjusted 4 Alarm icon blinks in case of alarm...

Страница 4: ...select the number 0 or 1 and confirm Selecting 0 enables to change screen backlight functions without restoring factory defaults Selecting 1 restores factory settings bl Backlight will be displayed an...

Страница 5: ...gh to prevent the boiler temperature rise 6 Time interval between successive blow throughs This is the time passing between the end of the blow through cycle and the start of a new cycle It should be...

Страница 6: ...t then press it and hold down until the blower is started turn the controller power off and on Firing up is terminated if the boiler temperature is lower than the set temperature 1 by at most a half o...

Страница 7: ...The CH pump is turned off if the boiler temperature drops below the preset value by a half of the preset hysteresis T boiler TCH HCH 2 Power Alarm Temperature In case the temperature measured by the...

Страница 8: ...oad 2 A 230 V 50 Hz Maximum blower output load 0 5 A 230 V 50 Hz Maximum power consumption 1 6 W Temperature measurement range from 5 C to 110 C CH temperature adjustment range from 20 C to 80 C Boile...

Страница 9: ...e every effort to ensure that this controller lifetime is as long as possible However the device is subject to natural wear If the device would not meet your requirements any more you are kindly reque...

Страница 10: ...y by the manufacturer or by other party clearly authorized by the manufacturer 5 Warranty becomes invalidated in case of any mechanical damage incorrect operation and or making any repairs by unauthor...

Отзывы: