ATTENTION:  The  controller  will  not  turn  the  blower  on  automatically  if  it  was 
previously manually turned off by the user.

 

12.

 

CONTROLLER OPERATION 

The boiler temperature is maintained by adjusting the amount of air blown and by controlling 
the CH pump.  
In  the  firing-up  mode  when  the  temperature  is  low  and  the  boiler  may  sweat,  the  blower  is 
operating  with  its  full  power  (determined  by  setting  No. 4).  Thus  the  firing-up  period  is  as 
short as possible. 
If  the  boiler  temperature  is  close  to  the  set  temperature,  within  the  hysteresis  range,  the 
controller  adjusts  the  air  flow  smoothly.  The  range  of  the  blower  power  control  is  limited  by 
two settings: the minimum blower power (3) and the maximum blower power (4). 
Exceeding  the  boiler  temperature  results  in  turning  into  the  blow-through  operation.  In  this 
operation  mode  the  blower  is  started  only  to  remove  combustion  gases  out  of  the  furnace. 
Blow-through cycle parameters should be set so that the boiler temperature drops to the level 
at which the blower operates with a linear rotational speed adjustment. 
If  the  boiler  temperature  exceeds  the  alarm  temperature,  the  blower  is  turned  off 
permanently. Display blinking indicates overheating. 
The  boiler  temperature  drop  below  the  shutdown  temperature  setting  (setting  No. 10)  turns 
the blower off. The pump operates according to the setting (No. 7). 
The CH pump is turned on if the boiler temperature exceeds the preset value by a half of the 
set hysteresis T 

boiler

 

 T

CH

 + H

CH 

/2 

The CH pump is turned off if the boiler temperature drops below the preset value by a half of 
the preset hysteresis T 

boiler

 

 T

CH

 - H

CH 

/2

 

Power Alarm Temperature

 

In  case  the  temperature  measured  by  the  boiler  sensor  exceeds  the  alarm  temperature 
(90 

°C),  the  blow

-throughs  are  turned  off,  and  additionally  the  thermal  protection  feature 

interrupts the blower power supply until the temperature drops to 60 

°C.

 

Frost protection

 

The frost protection function is activated when the temperature of the sensor falls to 4 

°C. 

If 

the  boiler  sensor  (CH)  reaches  such  temperature,  the  CH  pump  is  activated  and  "AF"  letters 
(Anti-Freeze) are displayed.

 

13.

 

ANTI-STOP 

Each time the controller is turned on, the ANTI-STOP function immediately turns the pump on 
for 30 seconds (also after restoring factory defaults or change of the backlight type); later the 
operation is repeated every 14 days. "AS" letters are blinking on the display while the function 
is active. 
Any alarm generated while the ANTI-STOP function is active (overheating or sensor damage) 
suspends the function operation until the alarm is over. 

14.

 

TROUBLESHOOTING 

Device does not work 

Burnt fuse or ROM failure 

 send the device to the service. 

The display blinks along with the sensor icon, "Sh" or "OP" letters appear 

Sensor  circuit  shorted  (

Sh

)  or  opened  (

OP

  check  the  adequate  sensor  cable  or  send  the 

device along with the sensors to the service. 

Pump or blower does not work 

Wrong  connection 

  make  sure  that  the  icons  are  displayed.  If  yes,  then  check  the 

connections. 
Setting  error 

  check  whether  the  blower  is  not  turned  off  manually  (section 11),  check  the 

settings. Restore factory settings (section 8). 
Thermal protection activation 

 wait for the temperature decrease. 

Содержание 11W

Страница 1: ...urnace and controls the operation of the CH circulation pump EUROSTER 11W controller is equipped with an ANTI STOP function that prevents seizing of an idle pump rotor It automatically turns the pump...

Страница 2: ...n the boiler in a point specially designed for that purpose or on an unshielded outlet pipe of the CH boiler as close to the boiler as possible using hose clip tighten the sensor to the pipe and cover...

Страница 3: ...ter displayed while previewing or changing the setting 2 Boiler temperature sensor icon 3 Manual operation mode icon lit while the temperature is manually adjusted 4 Alarm icon blinks in case of alarm...

Страница 4: ...select the number 0 or 1 and confirm Selecting 0 enables to change screen backlight functions without restoring factory defaults Selecting 1 restores factory settings bl Backlight will be displayed an...

Страница 5: ...gh to prevent the boiler temperature rise 6 Time interval between successive blow throughs This is the time passing between the end of the blow through cycle and the start of a new cycle It should be...

Страница 6: ...t then press it and hold down until the blower is started turn the controller power off and on Firing up is terminated if the boiler temperature is lower than the set temperature 1 by at most a half o...

Страница 7: ...The CH pump is turned off if the boiler temperature drops below the preset value by a half of the preset hysteresis T boiler TCH HCH 2 Power Alarm Temperature In case the temperature measured by the...

Страница 8: ...oad 2 A 230 V 50 Hz Maximum blower output load 0 5 A 230 V 50 Hz Maximum power consumption 1 6 W Temperature measurement range from 5 C to 110 C CH temperature adjustment range from 20 C to 80 C Boile...

Страница 9: ...e every effort to ensure that this controller lifetime is as long as possible However the device is subject to natural wear If the device would not meet your requirements any more you are kindly reque...

Страница 10: ...y by the manufacturer or by other party clearly authorized by the manufacturer 5 Warranty becomes invalidated in case of any mechanical damage incorrect operation and or making any repairs by unauthor...

Отзывы: