JVF-M2 Series Outdoor Gas Fireplace
IGM2S-190417
INSTALLATION
ROUGH OPENING / FRAMING
A wall switch is included in a water-tight control box. Installation of the control box must be where children
cannot reach for safety reasons.
While combustible framing is permitted, metal
framing is more appropriate for an outdoor
enclosure. A typical installation is shown.
The fireplace is then placed in the framing.
The facing is applied to the framing.
B
C
A
ROUGH OPENING DIMENSIONS
Dimension
JVF-60-M2-S
JVF-60-M2-ST
A (Width)
693/4” (1772
mm)
693/4” (1772
mm)
B (Height)
32” (813
mm)
32” (813
mm)
C (Depth)
18” (457
mm)
18” (457
mm)
Accumulated rain water will drain from a 7/8” (22.3mm) opening in the
center rear of the fireplace bottom.
This opening must not be blocked
see Figures 19 & 20 for drain placement.
The water which runs through
this opening will accumulate in the base of your enclosure and
must
be
allowed to drain away from the enclosure. An appropriate length of 11/2”
- 2” PVC pipe installed at the base of the enclosure which runs down and
out, is recommended. These openings must be checked for blockage
periodically.
FRONT
FIGURE 19: J-M2 SINGLE SIDED
FIGURE 15
FIGURE 16
FIGURE 17
FIGURE 18
FIGURE 20: J-M2 SEE-THROUGH
FRONT
Control
Control