H Series
Vent Free Gas Fireplace European
Home
.com
GAS INSTALLATION
18
Figure 9.
Gas Supply Opening On Left Side (see text)
45/8”x7” Opening for HVF-42, HVF-60, HVF-72,
HVF-42-LC, HVF-42-RC Gas Connection
INSTALL THE GAS SUPPLY
For the HVF-42, HVF-60 and HVF-72 models, a 45/8” x 7” opening in the lower left side is provided for the gas
supply.
The gas supply piping should have a separate gas shutoff valve and a capped,
1/8
” pipe tapping upstream of
the valve for the purpose of reading pressure. A service shutoff valve must be placed within six feet of the
fireplace gas control valve.
The gas supply line must terminate with a
1/2
” male flare fitting.
The fireplace must be isolated from the gas supply system by closing the service valve during any pressure
testing of the gas supply system at test pressures equal to or less than
1/2
psi (3.5 kPa). Verify the gas pressure
using the upstream
1/8
” pipe tap.
The installation of this fireplace must conform with local codes or, in the absence of local codes, with the
National Fuel Gas Code, ANSI Z223.1.
The
H Series Vent Free Gas Fireplace
is shipped from the factory for use with natural gas
ONLY
.
Conversion to another fuel is
NOT
permitted.
This product must be installed by a licensed plumber or gasfitter when installed within the
Commonwealth of Massachusetts.
Note
51/2”
215/16”
Fireplace
Opening