DV 52 ST See-thru Gas Fireplace

rev.110329

Installation

Installing The Gas Line

The gas line must be installed before finishing the 

DV 52 ST

 Fireplace. 

Natural Gas

 

requires a minimum  inlet gas supply  pressure of 5.5" w.c. and a manifold pressure of 
3.5" w.c. 

Propane Gas

 requires a minimum inlet gas supply pressure of 11" w.c. and 

a manifold pressure of 10" w.c. Provision must also be made for a 1/8" N.P.T. plugged 
tapping and be accessible for test gauge connection immediately upstream of the 
gas supply controls to the appliance. The fireplace gas connection and the main 
operating gas valve is located behind the removable trim at the bottom of the unit 
and need only be attached to the gas line  with an approved fitting, as required by 
the 

applicable installation codes

.

To access the fireplace gas connection the main burner must be removed 

as shown below in 

Figure 5a

.

• Only use gas shut-off valves approved for use by the state, province, region, or 
governing body, in which the appliance is being installed, or as required by the 
applicable installation codes.
• Flexible gas connectors must not exceed 3 feet in length, unless it is allowable  within 
applicable installation codes.
The appliance and its individual shut-off valve must be disconnected from the gas 

Note:

  After gas line is connected, 

each 

appliance connection

,

 valve and 

valve train

 must be checked while under normal operating pressure 

with either a liquid solution, or leak detection device, to locate any 
source of leak. Tighten any areas where bubbling appears or leak is 
detected until bubbling stops completely or leak is no longer detected. 

DO  NOT use a flame of any kind to test for leaks.

Figure 5a.  

Gas line access.

supply piping system during any pressure testing of that system at test pressures in 
excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its 
individual manual shut-off valve during any pressure testing of the gas supply piping 
system at test pressures equal to or less than 1/2 psig (3.5 kPa).

Vent  Installation

This section covers the installation of direct venting and terminations. 

Installation Requirements

• 

DV 52 ST fireplaces are certified for use with European Home 5"/8" venting components.

• 

Minimum clearance to combustible construction around the vent pipe is 1" on all sides, 
except on horizontal venting where the top of the pipe must have a clearance of at least 2".

• 

Use only certified European Home vent components. (Use of other parts will void the 
European Home warranty, and may impede the operation of the fireplace.)

• 

All joints must be secured with a minimum of two screws per joint

• 

Vent terminations must not be recessed in walls or siding

• 

Horizontal runs must be supported by a minimum of two supports per horizontal run. A 
minimum of one screw on each side of support is also required

• 

Flex vent sections may be stretched up to 50% of their total length (e.g. a 24" section 
may be stretched to 36")

• 

Flex vent sections over 6 feet must fall within the limits set by the venting graph and must 
have a minimum vertical rise of 3 inches per foot of flex.

• 

Solid vent sections may be cut less than half way from the female end

• 

Venting components can be used in any combination of solid/rigid pipe or flex pipe and 
in any orientation - male connectors can face in any direction

Installing The Remote Switch

The 

DV 52 ST

 gas valve, located behind the lower horizontal panel, may be connected 

to a wall switch. The valve generates its own power on

 a millivolt circuit. Use only 

low voltage wire, and DO NOT

 connect any external power to it.

Note:

  The switch location must not exceed 30' from the fireplace.

Gasline Access

0.875

dia.

6

to center

2 1/2

 Cautions: 

• 

Vent terminations can be very hot. If the termination is less than 
7 feet above a public walkway, it should be fitted with a certified 
European Home Heat Guard. (Part no. PTKOG).

• 

Do  not  obstruct,  or  attempt  to  conceal,  the  vent  termination.  

These actions will affect the operation of the fireplace, and may 

be hazardous.

• 

In heavy snow areas, take extra care to prevent snow buildup from 

obstructing the vent termination.

• 

Use European Home VSS Vinyl Shield when using on applications 

with vinyl siding to guard against possible damage.

Содержание DV 52 ST

Страница 1: ... cause injury or property damage Refer to this manual For assistance or additional information consult a qualifiedinstaller serviceagencyorthe gassupplier Warning What to do if you smell gas Donottrytolightanyappliance Donottouchanyelectricalswitch do notuseanyphoneinyourbuilding Immediatelycallyourgassupplier fromaneighbor sphone Followthe gassupplier sinstructions Ifyoucannotreachyourgassupplier...

Страница 2: ...place will give you years of durable reliable use Welcome to the European Home family of gas fireplace products SafetyAlertKey DANGER Indicates a hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a hazardous situation which if not avoided could result...

Страница 3: ...stotheNationalFuelGasCode ANSIZ223 1 1988 Iftheoptionalair circulating fanisinstalled itmustbegroundedinaccordancewithlocalcodesor intheabsence of local codes with the National Electrical Code ANSI NFPA 70 1987 Within the State of Massachusetts this fireplace must comply with NFPA 54 Chapter 10 CAUTION Due to its high operating temperatures the appliance should be located out of traffic and away f...

Страница 4: ...of thechasebeinsulatedwithavaporbarrier Thiswillreducethepossibilityofacold air convection current on the fireplace Figure 1 Fireplacedimensionsininches Clearance from the top of the to a combustible ceiling within the enclosure Refer to page 14 6 3 4 5 1 4 E B Figure 2a Securingthefireplacetotheframing Frame the fireplace cavity according to Figure2 Slide the fireplace into the cavity Tack four s...

Страница 5: ...iping system at test pressures equal to or less than 1 2 psig 3 5 kPa Vent Installation This section covers the installation of direct venting and terminations Installation Requirements DV52STfireplacesarecertifiedforusewithEuropeanHome5 8 ventingcomponents Minimum clearance to combustible construction around the vent pipe is 1 on all sides exceptonhorizontalventingwherethetopofthepipemusthaveacle...

Страница 6: ...erttheterminationintotheMOSRframeasshownhereandattachbyscrewing through the four pilot holes in the termination MSR PTO 4 5 8 PTO 4F 5 8 PTO 4 5 8 PTKOG 5 8 1 Ensure that the two long mounting brackets are facing the bottom of the termination See inset This will provide more heat protection at the top of the termination where temperatures are highest 2 Attach to the faceplate of the termination us...

Страница 7: ...ced on applicable models Vertical terminations must be installed minimum 2 two feet above the highest point where vent passes through the roof minimum 6 six feet from a mechanical air inlet minimum 18 11 2 feet from a parapet wall Maximumventheightis32feetabovefireplace Notethatflamecharacteristics will change if the maximum vent height is used Minimumclearances2 fromventtoallcombustiblematerialsm...

Страница 8: ...fsets 1offset two90 bends 32 PEXT PEXT PXT 10 Figure 18 ReducingVerticalVentfrom5 8 to4 7 Reduced Vertical Installation Available on Linear Power Vent models ONLY Itispossibletoreduceverticalventrunsfrom5 8 ventingto4 7 venting Reduced verticalventingmayonlybeusedwhenthelinear in line powerventisrequired This iscommonlyduetolongerthannormalventrunsorunusuallylonghorizontalventruns NOTES Alldimensi...

Страница 9: ...and walls above fireplace may be hot to touch Warning Whencoveringtheuppermetalportionofthefireplacewithanon combustiblematerial PleaseNote Thedecorativefacingmaterialsmaybesubjecttotemperaturesinexcess of 250 F This should be considered when selecting facing materials We recommend careful consideration be given to the effects of elevated mantel temperatureswhichmaybeinexcessofproductdesign forexa...

Страница 10: ... Door Buckles Figure 28 RemovingandInstallingtheHorizontalAccessPanel Locate the Door Buckles Figure 28b DoorBuckleTool 1 Step4 Firmly grasp hand hold end of door buckle tool and place the machined end in the slot under door frame as shown Figure 28c Step2 Step3 Step1 Remove the horizontal cover by plac ing fingers in both finger holes then pushing away from you and lifting out Place it aside duri...

Страница 11: ...wayfromthefrontofthefireplace SeeFigure28g Placethe doorasideinasafeplacewhilemaintenanceand orcleaningisbeingperformed Figure 28g Removingandinstallingtheglassdoors BothSidesTypical Removing the Door Figure 29 Installationwithglassbeads DV52ST WARNING Do not attempt to clean glass when hot Do not clean glass with abrasive materials as any glass etching may cause premature glass failure Do not ope...

Страница 12: ...as control knob slightly and turn clockwise to Off Do not force 4 Replace the lower horizontal access panel 1 Turn off remote switch 2 Lift out the lower horizontal access panel 1 STOP Read the safety information above on this label 2 Lift out the lower horizontal access panel 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas including ne...

Страница 13: ...call your gas supplier from a neighbor s phone Fol low the gas supplier s instructions If you cannot reach your gas supplier call the Fire Department C Use only your hand to push in or turn the gas control knob Never use 1 Turn off remote switch 2 Remove the lower horizontal access panel 3 Turn the incoming gas control valve to Off 4 Replace the lower horizontal access panel 1 STOP Read the safety...

Страница 14: ...flames Toadjusttheflames locatetheblackknobmarked Hi Lo inthecentreof the gas control valve See Figure32 The front burners are not adjustable To raise the flame height turn the black knob located behind the lower trim counter clockwise To lower the flame height turn clockwise Figure 32 Hi Lo AdjustmentontheDV52STgasvalve Cleaning When the fireplace is first activated there may be some smoking and ...

Страница 15: ...g stops completely Figure 34 PilotBurner Troubleshooting The following is a troubleshooting chart of possible problems PROBLEM CORRECTIVE ACTION Noisy pilot flame Locate pilot adjustment screw on gas control valve Flame is decreased by turn ing adjustment screw clockwise Pilot won t ignite Disconnect remote wires and try to light pilot If pilot now works remote connections are faulty Check wiring ...

Страница 16: ...20 seconds and re connect the wall transformer and battery backup If your fireplace still does not operate correctly consult your installer Maintenance 1 2 DV52STE DV 52 ST Spare Parts DV 52 ST DV 52 ST E NG Gas Valve RGC1006 RGC3033 LP Gas Valve RGC1005 RGC3034 NG Pilot RPA020 RPA052 LP Pilot RPA021 RPA053 NG Burner RBLS201 LP Burner RBLS202 NG Orifice Side 2 51 DMS Center 2 52 DMS ROR LP Orifice...

Страница 17: ...pany 2 The European Home Gas Appliance must be subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liability It is expressly agreed and understood thatThe Company sole obligatio...

Страница 18: ...to service regulator vent outlet 3 feet minimum in the United States 6 feet 1 8m minimuminCanada L clearancetonon mechanicalairsupplyinlettobuildingorthecombustionairinlettoany otherappliance 16inches 41cm minimumforappliances 100000BTU H 30kW M clearancetomechanicalairsupplyinlet 6feet 1 8m minimum N clearanceabovepavedsidewalkorapaveddrivewaylocatedonpublicproperty 7feet 2 1m minimum P clearance...

Страница 19: ...y in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GASVENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection ...

Страница 20: ...EUROPEAN HOME a division of Europa Ja Inc 376 Washington St Suite 203 Malden MA 02148 tel 781 324 8383 fax 781 324 8384 www europeanhome com ...

Отзывы: