Amendment

 

 

 

  (Gas Fireplace / Equipment sold in the State of Massachusetts)

 

 

 

 

   5.08: Modifications to NFPA-54, Chapter 10

 

(1) Revise NFPA-54 section 10.5.4.2

 

by adding a second exception as follows:

Existing chimneys shall be permitted to have their use continued when a gas conversion burner is installed, and shall be equipped with a manually reset device that will automatically shut off 
the gas to the burner in the event of a sustained back-draft

.

 

(2) Revise 10.8.3

 by 

adding the following additional requirements:

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or 
operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks 
and porches, the following requirements shall be satisfied: 

 

1. INSTALLATION OF CARBON MONOXIDE DETECTORS.

 

At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas 

fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the 
installing plumber or gas fitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or 
structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the 
installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up 
may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above 
requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

 

2. APPROVED CARBON MONOXIDE DETECTORS.

 

Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be 

ANSI/UL 2034 listed and IAS certified. 

 

3. SIGNAGE.

 

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in 

line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT 
DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

 

4. INSPECTION.

 The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspec-

tor observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4. 
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4: 

 

1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and 

 

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part 

for residential purposes.  

 

(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED

. When the manufacturer of Product Approved side wall horizontally vented 

gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the 
venting system shall include:
 

1. Detailed instructions for the installation of the venting system design or the venting system components; and

 

2. A complete parts list for the venting system design or venting system. 

 

(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED

. When the manufacturer of a Product Approved side wall horizontally 

vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
 

1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and 

 

2. The “special venting systems”

 shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instruc-

tions. 
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all 
venting design instructions shall remain with the appliance or equipment at the completion of the installation.

 

(3) After NFPA-54 section 10.10.4.2

 add a new section 10.10.4.3 as follows:

When more than four gas appliances are to be vented through a common gas vent or common horizontal vent manifold, a plan of the proposed vent installation shall be submitted to the 
Inspector and the serving gas supplier for review and approval.

Extraction from: Massachusetts Rules and Regulations

5.00: Amendments To 2002 Edition Of ANSI Z223.1-NFPA-54

Appendix B - State of Massachusetts

Содержание DV 52 ST

Страница 1: ... cause injury or property damage Refer to this manual For assistance or additional information consult a qualifiedinstaller serviceagencyorthe gassupplier Warning What to do if you smell gas Donottrytolightanyappliance Donottouchanyelectricalswitch do notuseanyphoneinyourbuilding Immediatelycallyourgassupplier fromaneighbor sphone Followthe gassupplier sinstructions Ifyoucannotreachyourgassupplier...

Страница 2: ...place will give you years of durable reliable use Welcome to the European Home family of gas fireplace products SafetyAlertKey DANGER Indicates a hazardous situation which if not avoided will result in death or serious injury WARNING Indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a hazardous situation which if not avoided could result...

Страница 3: ...stotheNationalFuelGasCode ANSIZ223 1 1988 Iftheoptionalair circulating fanisinstalled itmustbegroundedinaccordancewithlocalcodesor intheabsence of local codes with the National Electrical Code ANSI NFPA 70 1987 Within the State of Massachusetts this fireplace must comply with NFPA 54 Chapter 10 CAUTION Due to its high operating temperatures the appliance should be located out of traffic and away f...

Страница 4: ...of thechasebeinsulatedwithavaporbarrier Thiswillreducethepossibilityofacold air convection current on the fireplace Figure 1 Fireplacedimensionsininches Clearance from the top of the to a combustible ceiling within the enclosure Refer to page 14 6 3 4 5 1 4 E B Figure 2a Securingthefireplacetotheframing Frame the fireplace cavity according to Figure2 Slide the fireplace into the cavity Tack four s...

Страница 5: ...iping system at test pressures equal to or less than 1 2 psig 3 5 kPa Vent Installation This section covers the installation of direct venting and terminations Installation Requirements DV52STfireplacesarecertifiedforusewithEuropeanHome5 8 ventingcomponents Minimum clearance to combustible construction around the vent pipe is 1 on all sides exceptonhorizontalventingwherethetopofthepipemusthaveacle...

Страница 6: ...erttheterminationintotheMOSRframeasshownhereandattachbyscrewing through the four pilot holes in the termination MSR PTO 4 5 8 PTO 4F 5 8 PTO 4 5 8 PTKOG 5 8 1 Ensure that the two long mounting brackets are facing the bottom of the termination See inset This will provide more heat protection at the top of the termination where temperatures are highest 2 Attach to the faceplate of the termination us...

Страница 7: ...ced on applicable models Vertical terminations must be installed minimum 2 two feet above the highest point where vent passes through the roof minimum 6 six feet from a mechanical air inlet minimum 18 11 2 feet from a parapet wall Maximumventheightis32feetabovefireplace Notethatflamecharacteristics will change if the maximum vent height is used Minimumclearances2 fromventtoallcombustiblematerialsm...

Страница 8: ...fsets 1offset two90 bends 32 PEXT PEXT PXT 10 Figure 18 ReducingVerticalVentfrom5 8 to4 7 Reduced Vertical Installation Available on Linear Power Vent models ONLY Itispossibletoreduceverticalventrunsfrom5 8 ventingto4 7 venting Reduced verticalventingmayonlybeusedwhenthelinear in line powerventisrequired This iscommonlyduetolongerthannormalventrunsorunusuallylonghorizontalventruns NOTES Alldimensi...

Страница 9: ...and walls above fireplace may be hot to touch Warning Whencoveringtheuppermetalportionofthefireplacewithanon combustiblematerial PleaseNote Thedecorativefacingmaterialsmaybesubjecttotemperaturesinexcess of 250 F This should be considered when selecting facing materials We recommend careful consideration be given to the effects of elevated mantel temperatureswhichmaybeinexcessofproductdesign forexa...

Страница 10: ... Door Buckles Figure 28 RemovingandInstallingtheHorizontalAccessPanel Locate the Door Buckles Figure 28b DoorBuckleTool 1 Step4 Firmly grasp hand hold end of door buckle tool and place the machined end in the slot under door frame as shown Figure 28c Step2 Step3 Step1 Remove the horizontal cover by plac ing fingers in both finger holes then pushing away from you and lifting out Place it aside duri...

Страница 11: ...wayfromthefrontofthefireplace SeeFigure28g Placethe doorasideinasafeplacewhilemaintenanceand orcleaningisbeingperformed Figure 28g Removingandinstallingtheglassdoors BothSidesTypical Removing the Door Figure 29 Installationwithglassbeads DV52ST WARNING Do not attempt to clean glass when hot Do not clean glass with abrasive materials as any glass etching may cause premature glass failure Do not ope...

Страница 12: ...as control knob slightly and turn clockwise to Off Do not force 4 Replace the lower horizontal access panel 1 Turn off remote switch 2 Lift out the lower horizontal access panel 1 STOP Read the safety information above on this label 2 Lift out the lower horizontal access panel 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas including ne...

Страница 13: ...call your gas supplier from a neighbor s phone Fol low the gas supplier s instructions If you cannot reach your gas supplier call the Fire Department C Use only your hand to push in or turn the gas control knob Never use 1 Turn off remote switch 2 Remove the lower horizontal access panel 3 Turn the incoming gas control valve to Off 4 Replace the lower horizontal access panel 1 STOP Read the safety...

Страница 14: ...flames Toadjusttheflames locatetheblackknobmarked Hi Lo inthecentreof the gas control valve See Figure32 The front burners are not adjustable To raise the flame height turn the black knob located behind the lower trim counter clockwise To lower the flame height turn clockwise Figure 32 Hi Lo AdjustmentontheDV52STgasvalve Cleaning When the fireplace is first activated there may be some smoking and ...

Страница 15: ...g stops completely Figure 34 PilotBurner Troubleshooting The following is a troubleshooting chart of possible problems PROBLEM CORRECTIVE ACTION Noisy pilot flame Locate pilot adjustment screw on gas control valve Flame is decreased by turn ing adjustment screw clockwise Pilot won t ignite Disconnect remote wires and try to light pilot If pilot now works remote connections are faulty Check wiring ...

Страница 16: ...20 seconds and re connect the wall transformer and battery backup If your fireplace still does not operate correctly consult your installer Maintenance 1 2 DV52STE DV 52 ST Spare Parts DV 52 ST DV 52 ST E NG Gas Valve RGC1006 RGC3033 LP Gas Valve RGC1005 RGC3034 NG Pilot RPA020 RPA052 LP Pilot RPA021 RPA053 NG Burner RBLS201 LP Burner RBLS202 NG Orifice Side 2 51 DMS Center 2 52 DMS ROR LP Orifice...

Страница 17: ...pany 2 The European Home Gas Appliance must be subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liability It is expressly agreed and understood thatThe Company sole obligatio...

Страница 18: ...to service regulator vent outlet 3 feet minimum in the United States 6 feet 1 8m minimuminCanada L clearancetonon mechanicalairsupplyinlettobuildingorthecombustionairinlettoany otherappliance 16inches 41cm minimumforappliances 100000BTU H 30kW M clearancetomechanicalairsupplyinlet 6feet 1 8m minimum N clearanceabovepavedsidewalkorapaveddrivewaylocatedonpublicproperty 7feet 2 1m minimum P clearance...

Страница 19: ...y in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GASVENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection ...

Страница 20: ...EUROPEAN HOME a division of Europa Ja Inc 376 Washington St Suite 203 Malden MA 02148 tel 781 324 8383 fax 781 324 8384 www europeanhome com ...

Отзывы: