00139830.DOC, Version 1.0
15/16
6. CLEANING AND MAINTENANCE
The operator has to make sure that safety-relating and machine-technical installations are inspected by an
expert after every four years in the course of an acceptance test.
The operator has to make sure that safety-relating and machine-technical installations are inspected by a
skilled person once a year.
The following points have to be considered during the inspection:
1) All screws used for installing the devices or parts of the device have to be tightly connected and must not
be corroded.
2) The electric power supply cables must not show any damages, material fatigue (e.g. porous cables) or
sediments. Further instructions depending on the installation spot and usage have to be adhered by a
skilled installer and any safety problems have to be removed.
Disconnect from mains before starting maintenance operation!
DANGER TO LIFE!
We recommend a frequent cleaning of the device. Please use a moist, lint-free cloth. Never use alcohol or
solvents!
There are no serviceable parts inside the device. Maintenance and service operations are only to be carried
out by authorized dealers.
Should you need any spare parts, please use genuine parts.
The examination intervals for mobile electrical devices (German DGUV-V3) must be kept.
The operator has to make sure that the electrical devices are examined by an electrician before taking into
operation for the first time and after changes before taking into operation another time.
Electrical devices must only be taken into operation in a perfect condition and must be kept this way.
For keeping the perfect condition, electrical devices must repeatedly be approved in accordance with the
instructions given in the electro-technical guidelines.
A qualified electrician is responsible for the correct examinations.
Mobile electrical devices, extension cords with plugs, power cables with plugs and mobile cables with plugs
and permanent installation must be approved by an expert every three months.
Should you have further questions, please contact your dealer.
7. TECHNICAL SPECIFICATIONS
Power supply:
380-400V AC, 50Hz
Power connection:
Fixed power supply cord with CEE 32A 5-pin
Power output:
1 x CEE 32A 5-pol (F) recessed mounting Bypass
6 x Safety contact (F), hinged lid mounting version fused
2 x CEE 16A 5-pol (F) recessed mounting fused
Protection:
1 x fault-current circuit breaker (FI) Type B 40A/0,03A 4-pol
2 x circuit breaker C 16A 3-pol
3 x circuit breaker C 16A 1-pol
Phase status display:
3
Housing design:
(19") 48.3 cm rack installation 3 U
Dimensions:
Width: 48.3 cm
Depth: 29.5 cm
Height: 13.35 cm
Weight:
6.05 kg
All information is subject to change without prior notice. © 10.06.2022