EUROHEAT
DISTRIBUTORS (H.B.S) LTD. Dec 2004
E & OE Instructions Part number IN1084 Ed D
32
Commissioning
a)
Carry out a gas leak test as regulations require.
b)
Ensure that all openable doors and windows in the room are shut, light the stove and operate
on maximum for five minutes. Position a smoke match just beside the thermocouple TTB (see
diagram) and check that all the smoke is drawn into the opening to the flue diverter.
IF SPILLAGE IS STILL OBSERVED, THERE MAY BE A PROBLEM WITH THE FLUE SYSTEM OR
CHIMNEY, DISCONNECT THE APPLIANCE UNTIL THE PROBLEM HAS BEEN IDENTIFIED.
Note:
If there are any extractor fans in the room or adjacent rooms, these must be running at maximum
setting with all interconnecting doors left open, and the spillage test repeated.
c)
Carry out a gas operating pressure test. Attach a manometer to the operating pressure
test nipple. With the appliance operating at maximum, observe the operating pressure. Adjust if
required.
d)
Carry out a low burn operating pressure test. Attach a manometer to the operating pressure
test nipple. Turn the gas valve control knob to the minimum flame size. Observe the operating
pressure.
e)
Carry out a gas supply pressure test with the appliance operating. Attach a manometer to the
supply pressure test nipple. If the pressure is below requirements inspect gas pipe installation for
possible problems.