Operating Instructions

Safety Switch NZ.VZ…AS 

Function test

 WARNING

Fatal injury due to faults during the function test.

 

f

Before carrying out the function test, make sure 

that there are no persons in the danger area.

 

f

Observe the valid accident prevention regula-

tions.

Check the device for correct function after installa-

tion and after every fault.
Proceed as follows:

Mechanical function test

The actuator must slide easily into the actuating 

head. Close the safety guard several times to check 

the function.

Electrical function test

1.  Switch on operating voltage.
2.  Close all safety guards.

¨

¨

The machine must not start automatically.

3.  Start the machine function.
4.  Open the safety guard.

¨

¨

The machine must switch off and it must not be 

possible to start it as long as the safety guard 

is open.

Repeat steps 2 - 4 for each safety guard.

Inspection and service

 WARNING

Danger of severe injuries due to the loss of the 

safety function.

 

f

If damage or wear is found, the complete switch 

and actuator assembly must be replaced. Re-

placement of individual parts or assemblies is 

not permitted.

 

f

Check the device for proper function at regular 

intervals and after every fault. For informa-

tion about possible time intervals, refer to 

EN ISO 14119:2013, section 8.2.

Inspection of the following is necessary to ensure 

trouble-free long-term operation:

 

f

correct switching function

 

f

secure mounting of all components

 

f

damage, heavy contamination, dirt and wear

 

f

sealing of cable entry

 

f

loose cable connections or plug connectors.

Information

:

 

The year of manufacture can be seen 

in the bottom, right corner of the type label.

Exclusion of liability and warranty

In case of failure to comply with the conditions for 

correct use stated above, or if the safety regula-

tions are not followed, or if any servicing is not 

performed as required, liability will be excluded and 

the warranty void.

Notes about 

For use and operation as per the requirements 

of 

 (UL), an isolating transformer or a power 

supply with secondary overcurrent protection (3 A) 

must be used.

EC declaration of conformity

The manufacturer named below herewith declares 

that the product fulfills the provisions of the direc-

tive(s) listed below and that the related standards 

have been applied.
EUCHNER GmbH + Co. KG 

Kohlhammerstr. 16 

D-70771 Leinfelden-Echterdingen
Directives applied:

 

f

Machinery directive 2006/42/EC

Standards applied:

 

f

EN 60947-5-1:2004 + Cor.:2005 + A1:2009

 

f

EN 1088:1995+A2:2008

 

f

EN 14119:2013

The original EC declaration of conformity can also 

be found at: www.euchner.de

Service

If service support is required, please contact:
EUCHNER GmbH + Co. KG

Kohlhammerstraße 16

D-70771 Leinfelden-Echterdingen

Service telephone

:

+49 711 7597-500

Fax

:

+49 711 753316

E‑mail

:

[email protected]

Internet

:

www.euchner.de

Technical data

Parameter

Value

Housing material

Anodized die-cast alloy

Degree of protection  

acc. to IEC 60529

IP67, mating connector inserted

Mechanical life

2 x 10

6

 operating cycles

Ambient temperature

-20 … +55 °C

Degree of contamination

(external, acc. to EN 60947-1) 3 (industrial)
Installation position

Any

Approach speed, max.

20 m/min

Extraction force

35 N

Retention force

10 N

Actuating force, max.

35 N

Actuation frequency

7000/h

Switching principle

2 positively driven NC contacts, 

slow-action switching contact

Connection

Plug connector M12, 4-pin

Weight

Approx. 0.35 kg

AS‑Interface data

 acc. to 

AS-Interface specification 2.1

EA code: 7

ID code: B

Operating voltage AS-Interface DC 22.5 ... 31.6 V
Total current consumption, max. 45 mA
Valid AS-Interface addresses

1 - 31

AS‑Interface inputs

Acc. to AS-Interface Safety at Work

Positively driven NC contact 1 D0, D1
Positively driven NC contact 2 D2, D3

AS‑Interface outputs

D1

Red LED, 1 = LED on

D2

Green LED, 1 = LED on

AS-Interface LED Power

Green, AS-Interface Power on

AS-Interface LED Fault

Red, offline phase or address 0“

Reliability values acc. to EN ISO 13849‑1

B

10d

4.5 x 10

6

Status table

Programming

State

D0, D1

D2, D3

Monitor diagnosis

Dual channel  

dependent 

Synchronization time 3 s

Safety guard closed

Code sequence

Green

If start-up test selected:

Yellow flashing on start-up

Intermediate state during opening or closing of the safety guard.  

Switch S1 (internal) open

Half-sequence

00

During opening: Yellow flashing

During closing: Red

After expiration of the synchronization time: 

Yellow flashing

Intermediate state during opening or closing of the safety guard.  

Switch S2 (internal) open

00

Half-sequence

Safety guard open

00

00

Red

Address 0 or communication disrupted

Gray

Содержание NZ.VZ AS Series

Страница 1: ...utorisiertes Fachperso nal welches über spezielle Kenntnisse im Umgang mit Sicherheitsbauteilen verfügt Funktion Der Sicherheitsschalter überwacht die Stellung von beweglichen trennenden Schutzeinrichtungen Beim Einführen Herausziehen des Betätigers werden die Schaltkontakte betätigt Bei geschlossener Schutzeinrichtung sendet jeder NZ VZ AS über den AS Interface Bus eine schalter spezifische unver...

Страница 2: ...eine Spannungsversorgung mit sekundär em Überstromschutz 3 A verwendet werden EG Konformitätserklärung Der nachstehende Hersteller erklärt hiermit dass das Produkt in Übereinstimmung mit den Bestimmungen der nachfolgend aufgeführten Richtlinie n ist und dass die jeweiligen Normen zur Anwendung gelangt sind EUCHNER GmbH Co KG Kohlhammerstr 16 D 70771 Leinfelden Echterdingen Angewendete Richtlinien ...

Страница 3: ...ltvorgang beendet Betätiger muss bis zu diesem Punkt eingeführt werden um eine sichere Schal tung zu gewährleisten Zum Ausschalten muss der Betätiger mindestens bis Punkt a zurückgezogen werden Bild 4 Minimale Türradien Betätiger Türradius min mm Betaetiger Z G 1000 Radiusbetätiger Z R 200 Radiusbetätiger Z L 200 Radiusbetätiger Z C2194 200 Radiusbetätiger Z U 165 Radiusbetätiger Z O 165 Radiusbet...

Страница 4: ...ed personnel possessing special knowledge about handling safety components Function The safety switch monitors the position of movable safety guards The switching contacts are actuated on the insertion removal of the actuator When the safety guard is closed each NZ VZ AS transmits a switch specific unique safety code sequence with 8 x 4 bits via the AS Interface bus This code sequence is evaluated...

Страница 5: ...fills the provisions of the direc tive s listed below and that the related standards have been applied EUCHNER GmbH Co KG Kohlhammerstr 16 D 70771 Leinfelden Echterdingen Directives applied f f Machinery directive 2006 42 EC Standards applied f f EN 60947 5 1 2004 Cor 2005 A1 2009 f f EN 1088 1995 A2 2008 f f EN 14119 2013 The original EC declaration of conformity can also be found at www euchner ...

Страница 6: ... the guide slot but a function is not triggered b Switching operation completed actuator must be inserted to this point to ensure reliable switching The actuator must be withdrawn at least to point a for switching off Figure 4 Minimum door radii Actuator Door radius min mm Actuator Z G 1000 Hinged actuator Z R 200 Hinged actuator Z L 200 Hinged actuator Z C2194 200 Hinged actuator Z U 165 Hinged a...

Отзывы: