Operating Instructions
Safety Switch NZ.VZ…AS
Function test
WARNING
Fatal injury due to faults during the function test.
f
Before carrying out the function test, make sure
that there are no persons in the danger area.
f
Observe the valid accident prevention regula-
tions.
Check the device for correct function after installa-
tion and after every fault.
Proceed as follows:
Mechanical function test
The actuator must slide easily into the actuating
head. Close the safety guard several times to check
the function.
Electrical function test
1. Switch on operating voltage.
2. Close all safety guards.
¨
¨
The machine must not start automatically.
3. Start the machine function.
4. Open the safety guard.
¨
¨
The machine must switch off and it must not be
possible to start it as long as the safety guard
is open.
Repeat steps 2 - 4 for each safety guard.
Inspection and service
WARNING
Danger of severe injuries due to the loss of the
safety function.
f
If damage or wear is found, the complete switch
and actuator assembly must be replaced. Re-
placement of individual parts or assemblies is
not permitted.
f
Check the device for proper function at regular
intervals and after every fault. For informa-
tion about possible time intervals, refer to
EN ISO 14119:2013, section 8.2.
Inspection of the following is necessary to ensure
trouble-free long-term operation:
f
correct switching function
f
secure mounting of all components
f
damage, heavy contamination, dirt and wear
f
sealing of cable entry
f
loose cable connections or plug connectors.
Information
:
The year of manufacture can be seen
in the bottom, right corner of the type label.
Exclusion of liability and warranty
In case of failure to comply with the conditions for
correct use stated above, or if the safety regula-
tions are not followed, or if any servicing is not
performed as required, liability will be excluded and
the warranty void.
Notes about
For use and operation as per the requirements
of
(UL), an isolating transformer or a power
supply with secondary overcurrent protection (3 A)
must be used.
EC declaration of conformity
The manufacturer named below herewith declares
that the product fulfills the provisions of the direc-
tive(s) listed below and that the related standards
have been applied.
EUCHNER GmbH + Co. KG
Kohlhammerstr. 16
D-70771 Leinfelden-Echterdingen
Directives applied:
f
Machinery directive 2006/42/EC
Standards applied:
f
EN 60947-5-1:2004 + Cor.:2005 + A1:2009
f
EN 1088:1995+A2:2008
f
EN 14119:2013
The original EC declaration of conformity can also
be found at: www.euchner.de
Service
If service support is required, please contact:
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
D-70771 Leinfelden-Echterdingen
Service telephone
:
+49 711 7597-500
Fax
:
+49 711 753316
E‑mail
:
Internet
:
www.euchner.de
Technical data
Parameter
Value
Housing material
Anodized die-cast alloy
Degree of protection
acc. to IEC 60529
IP67, mating connector inserted
Mechanical life
2 x 10
6
operating cycles
Ambient temperature
-20 … +55 °C
Degree of contamination
(external, acc. to EN 60947-1) 3 (industrial)
Installation position
Any
Approach speed, max.
20 m/min
Extraction force
35 N
Retention force
10 N
Actuating force, max.
35 N
Actuation frequency
7000/h
Switching principle
2 positively driven NC contacts,
slow-action switching contact
Connection
Plug connector M12, 4-pin
Weight
Approx. 0.35 kg
AS‑Interface data
acc. to
AS-Interface specification 2.1
EA code: 7
ID code: B
Operating voltage AS-Interface DC 22.5 ... 31.6 V
Total current consumption, max. 45 mA
Valid AS-Interface addresses
1 - 31
AS‑Interface inputs
Acc. to AS-Interface Safety at Work
Positively driven NC contact 1 D0, D1
Positively driven NC contact 2 D2, D3
AS‑Interface outputs
D1
Red LED, 1 = LED on
D2
Green LED, 1 = LED on
AS-Interface LED Power
Green, AS-Interface Power on
AS-Interface LED Fault
Red, offline phase or address 0“
Reliability values acc. to EN ISO 13849‑1
B
10d
4.5 x 10
6
Status table
Programming
State
D0, D1
D2, D3
Monitor diagnosis
Dual channel
dependent
Synchronization time 3 s
Safety guard closed
Code sequence
Green
If start-up test selected:
Yellow flashing on start-up
Intermediate state during opening or closing of the safety guard.
Switch S1 (internal) open
Half-sequence
00
During opening: Yellow flashing
During closing: Red
After expiration of the synchronization time:
Yellow flashing
Intermediate state during opening or closing of the safety guard.
Switch S2 (internal) open
00
Half-sequence
Safety guard open
00
00
Red
Address 0 or communication disrupted
–
Gray