11.7. Notes on operation with safe control systems
Please observe the following requirements for connection to safe control systems:
Ì
Use a common power supply for the control system and the connected interlocking modules.
Ì
The device tolerates voltage interruptions on UB of up to 5 ms. Tap the supply voltage directly from the power supply
unit. If the power supply is connected to a terminal of a safe control system, this output must provide sufficient electri-
cal current.
Ì
The safety outputs (FO1A and FO1B) can be connected to the safe inputs of a control system. Prerequisite: the input
must be suitable for pulsed safety signals (OSSD signals, e.g. from light grids). The control system must tolerate test
pulses on the input signals. This normally can be set up by parameter assignment in the control system. Observe the
notes of the control system manufacturer. For the pulse duration of your interlocking module, please refer to chapter
A detailed example of connecting and setting the parameters of the control system is available for many devices at
www.euchner.com in the area Download
¨
Applications
¨
MGBS. The features of the respective device are dealt with there
in greater detail.
4/8 F-DI
PWR
Supply of
the control
Safety Outputs
Door
Monitoring
Read Head
Actuator
Monitoring Outputs
FO1B
4
OI
5
Diagnostic
-B1
UB
2
1
n.c.
n.c.
8
0 V
UB
7
OD
6
FO1A
3
MGBS
1
2
-F2
-X1
DI4
DI0
DC24V
M
1
2
-F1
24V DC
0 V
24V DC
0 V
Figure 5:
Connection example for the connection to ET200