Operating Instructions

Safety Relay ESM-BA3..

What to do in case of a fault?

Device does not switch on:

 

f

Check the wiring by comparing it to the wiring 

diagrams.

 

f

Check the safety switch used for correct function 

and adjustment.

 

f

Check whether the emergency stop circuit is 

closed.

 

f

Check whether the start button (with manual start) 

is closed.

 

f

Check the operating voltage at A1 and A2.

 

f

Is the feedback loop closed?

Device cannot be switched on again after an 

emergency stop:

 

f

Check whether the emergency stop circuit was 

closed again.

 

f

Was the start button opened before closing of the 

emergency stop circuit (with manual start)?

 

f

Is the feedback loop closed?

If the fault persists, perform the steps listed under 

Setup procedure

.

If these steps do not remedy the fault either, return 

the device to the manufacturer for examination.

Opening the device is impermissible and will 

void the warranty.

Maintenance

The device must be checked once per month for 

proper function and for signs of tampering and 

bypassing of the safety function. The device is 

otherwise maintenance-free, provided that it was 

installed properly.

Disposal

Pay attention to the applicable national regulations 

and laws during disposal.

EU declaration of conformity

The declaration of conformity is part of the operating 

instructions, and it is included as a separate sheet 

with the device.
The EU declaration of conformity can also be found 

at: www.euchner.com

Service

If servicing is required, please contact:
EUCHNER GmbH + Co. KG

Kohlhammerstraße 16

70771 Leinfelden-Echterdingen

Germany

Service telephone

:

+49 711 7597-500

E-mail

:

[email protected]

Internet

:

www.euchner.com

Technical data

Parameter

Value

Version

ESM-BA301

ESM-BA302

ESM-BA303

Operating voltage

AC/DC 24 V

AC 115V

AC 230 V

Rated supply frequency

50 - 60 Hz

Permissible deviation

± 10%

Power consumption

DC 24 V

AC 230 V

Approx. 2.3 W

 Approx. 6.9 VA

Control voltage at S11

DC 24 V

Control current S11 … S14

Approx. 60 mA

Safety contacts

3 NO contacts

Monitoring contacts

1 NC contact

Max. switching voltage

AC 250 V

Safety contact breaking capacity

(13-14, 23-24, 33-34)

AC: 250 V, 2,000 VA, 8 A for ohm resistive load (6 operating cycles/minute)

250 V, 3 A for AC-15

DC: 40 V, 320 W, 8 A for ohm resistive load (6 operating cycles/minute)

24 V, 3 A, for DC-13

Max. cumulative current

15 A (13-14, 23-24, 33-34)

 1)

Monitoring contact breaking capacity 

(41-42)

AC: 250 V, 500 VA, 2 A for ohm resistive load

DC: 40 V, 80 W, 2 A for ohm resistive load

Minimum contact load

24 V, 5 mA

Contact fuses

10 A gG

Conductor cross-section

0.14 - 2.5 mm²

Max. length of control cable

1,000 m with 0.75 mm²

Contact material

AgSnO

2

Mech. contact life

Approx. 1 x 10

7

Test voltage

2.5 kV (control voltage/contacts)

Rated impulse withstand voltage,  

leakage paths/air gaps

4 kV (DIN VDE 0110-1)

Rated insulation voltage

250V

Degree of protection

IP20

Temperature range

-15 °C to +40 °C

 1)

Degree of contamination

2 (DIN VDE 0110-1)

Overvoltage category

3 (DIN VDE 0110-1)

Weight

Approx. 230 g

Mounting

Mounting rail according to DIN EN 60715 TH35

Reliability values according to EN ISO 13849-1 for all variants of the series ESM-BA3

 2)

Load (DC-13; 24 V)

≤ 0.1 A

≤ 1 A

≤ 2A

n

op

≤ 500,000 cycles

≤ 350,000 cycles

≤ 100,000 cycles

T

10D

20 years

Category

4

PL

e

PFH

D

1.2 x 10

-8

 1/h

1)  If several ESM-BA3.. are closely spaced under load, the max. cumulative current is 9 A at an ambient temperature of T = 20 °C, 3 A 

at  T = 30 °C and 1 A at T = 40 °C. If these currents are exceeded, a spacing of 5 mm between the devices must be observed.

2)  Additional data can be requested from the manufacturer for applications that deviate from these conditions.

Fixed terminals

Plug-in terminals

Fig. 4:  Dimension drawing for ESM-BA3..