Operating Instructions

Safety Relay ESM-BA3..

3

Subject to technical modifications; no r

esponsibility is accepted for the accuracy of this information.

 

© EUCHNER GmbH + Co. KG

 

2090073

-09

-07/22 V1.1.0 (translation of the original operating instructions)

Applications

Depending on the application or the result of the risk assessment according to DIN EN ISO 13849 1, the device must be wired as shown in Fig. 5 to Fig. 15.

Emergency stop circuit

Fig. 5:   Dual-channel emergency stop circuit with 

short circuit and ground fault monitoring 

(category 4, up to PL e).

Fig. 6:   Dual-channel emergency stop circuit with 

ground fault monitoring (category 3, up 

to PL d).

Fig. 7:   Single-channel emergency stop circuit with 

ground fault monitoring (category 1, up to 

PL c).

Notice:

In order to activate ground fault monitoring, S10 

must be connected to PE (protective earth) on the 

AC115/230V devices. With AC/DC 24 V, connect 

PE only to the power supply unit according to 

EN 60204-1.
Wire the start circuit in accordance with the applica-

tion according to Fig. 10 or Fig. 11.

Fig. 8:   Dual-channel sliding guard monitoring with 

short circuit and ground fault monitoring 

(category 4, up to PL e).

Fig. 9:   Dual-channel emergency stop circuit with 

pnp semiconductor outputs / OSSD outputs 

with short circuit detection (category 4, 

up to PL e).

Starting behavior

Fig. 10:   Monitored manual start. It is monitored 

that the start button was opened before 

the emergency stop buttons close (pre-

requisite: operating voltage must not be 

interrupted).

Fig. 11:  Automatic start. Max perm. delay during 

closing of the safety switches on S12 

and S13:
S12 before S13: 300 ms
S13 before S12: any

Feedback loop

Fig. 12:   Feedback loop. Monitoring of externally 

connected contactors or expansion mod-

ules.

Fig. 13:   Feedback loop with automatic start. Mon-

itoring of externally connected contactors 

or expansion modules.

Power supply and safety contacts

Fig. 14:   Connection of the power supply to terminals 

A1 and A2 (power supply according to the 

technical data).

Fig. 15:   Connection to switching loads on safety 

contacts (example contact configura-

tion. Differing according to device type. 

Switching voV corresponding to 

technical data).