Transponder-Coded Safety Switch CTP-LBI-AP
EN
6.5.
Guard locking on version CTP-LBI
(Guard locking actuated by spring force and released by power-ON)
Activating guard locking:
close guard; no voltage at control input IMP
Releasing guard locking:
apply voltage to control input IMP.
The spring-operated guard locking functions in accordance with the closed-circuit current principle. If the voltage is interrupted
at the solenoid, the guard locking remains active and the guard cannot be opened directly.
If the guard is opened when the power supply is interrupted and is then closed, the guard locking pin will be pushed down
and held in this position. This prevents people from being locked in unintentionally.
6.6.
Switching states
The detailed switching states for your switch can be found in the system status table. All safety outputs, monitoring outputs
and display LEDs are described there.
Guard closed and locked
IMP
IMM
Guard closed and not locked
IMP
IMM
Guard open
IMP
IMM
Control input IMP
off
on
(irrelevant)
Safety outputs FO1A and FO1B
on
off
off
Guard locking monitoring output OL
on
off
off
Door monitoring output OD
on
on
off