Operating Instructions
Transponder-Coded Safety Switch CTM-C2-BP/BR-FLX
32
(translation of the original operating instructions) MAN20001574-01-09/22
15.3. Error messages
Err
or code via IO-Link
LED indicator
Error
Troubleshooting
Ac-
knowl-
edging
errors
STATE
green
DIA
red
LOCK
yellow
Open/close door
Reset
Teach-in error
0x1F
1 x
Actuator removed from the actuating range prior to
the end of the teach-in operation.
Check whether the actuator is outside the actuating
range or in the limit range.
0x25
Disabled actuator detected during the teach-in oper-
ation:
The actuator was taught-in during the penultimate
teach-in operation and is disabled for the current
teach-in operation.
Repeat the teach-in operation with a new actuator
(see chapter
13.2. Actuator teach-in on page 27
Input error
0x2E
2 x
1x inverse
Different signal states at the safety inputs FI1A and
FI1B during operation.
Ì
Check wiring.
Ì
Check preceding device in the switch chain.
0x30
Different signal states at the safety inputs FI1A and
FI1B during the self-test.
0x31
0x32
Test pulses not detected at safety input FI1A or FI1B
during operation.
0x36
0x37
Test pulses not detected at safety input FI1A or FI1B
during self-test.
Transponder/read error
0x42
3 x
Invalid or faulty actuator detected during teach-in
operation.
Ì
The actuator is not intended for the current device
configuration.
Ì
The actuator’s data structure cannot be read. The
actuator is faulty.
Repeat teach-in operation with valid actuator (see
13.2. Actuator teach-in on page 27
).
Invalid or faulty actuator detected.
Ì
The actuator is not intended for the current device
configuration.
Ì
The actuator’s data structure cannot be read. The
actuator is faulty.
Remove the actuator. Error is reset automatically.
Output error
0x4C
0x4D
4 x
A HIGH signal is detected at safety output FO1A or
FO1B during the self-test.
Check wiring.
0x54
1x inverse
The voltage level at safety outputs FO1A and FO1B
during operation does not meet the requirements.
External voltage might be present.
Environment error
0x60
5 x
1x inverse
Supply voltage too high.
Decrease supply voltage.
0x61
Supply voltage too low.
Ì
Increase supply voltage.
Ì
Check system configuration: cable length, number of
devices in the switch chain.
0x62
Device temperature too high.
Observe the specified temperature range (see chapter
16. Technical data on page 34).
0x63
Device temperature too low.
Internal error
0x01
Internal device error
Restart the device. On repeated occurrence, contact
the manufacturer.