Operating Instructions Safety Systems
MGB-L..B-PN.-… (PROFINET) and With Data Structure Type A
12
(translation of the original operating instructions) 2114575-06-02/21
6.5.
Control of guard locking
From MGB version V2.36.4, the factory setting ensures that control is possible only from the safe control area.
By changing the parameters in the configuration tool of your control system, it can be set whether bit
O 16
(in the safe
data block for the MGB locking module) is evaluated as well.
Important!
The following applies to MGB-L2:
Control of the guard locking via the safe control area does not provide increased safety, as the de-
vice-internal control of the guard locking is only of single-channel design.
Important!
The following functions depend on the MGB version, the version of the GSD file and the settings made
there.
Compare the specified versions with those on your device and in your GSD file. The version number
of your MGB can be found on the type label (format: VX.XX.X).
MGB version
GSD version
Continue in section ...
up to and including V2.35.4
..._110026-
20110725
Case A
..._110026-
20110815
Case A
From V3.30.0
..._110026-
20110725
Case B
..._110026-
20110815
or newer
Case C
6.5.1. Case A
You have an MGB with a version number of V2.35.4 and a GSD file with a version number of ..._110026-20110725 or older.
Or you have an MGB with a version number of V2.35.4 and a GSD file with a version number from ..._110026-20110815.
The guard locking solenoid is controlled if
Ì
bit
O 16
OR
bit
SO 1 = 1
Truth table
PROFINET bit
PROFIsafe bit
Guard locking with
O 16
SO 1
MGB-L1...
MGB-L2...
0
0
Active
Inactive
0
1
Inactive
Active
1
0
Inactive
Active
1
1
Inactive
Active
What must be observed?
Guard locking can be controlled from the non-safe control area. The combination with the more up-to-date GSD file allows
a parameter to specify which bits are to be used for control. However, the device does not support this function. In other
words, the setting in your configuration software remains ineffective.