Fig. 31 Outside gypsum wall construction- mineral wool- stuffing box and fire protection mastic
and cement lime plate
EIS90
Screws has to be fixed in wall/ceiling construction.
(If it is needed use steel bracket).
Position:
1 Fire damper
2 Gypsum plate
3 Mineral wool
(type depending on the type of construction)
4 Stuffing box
(mineral stone wool min. density 140 kg/m³)
5 Fire protection mastic min. thickness 1 mm
6 Cement lime plate min. thickness 15 mm
(min. density 870 kg/m³)
7 Stone wool with one side stitched wire fencing
(min. density 105 kg/m³), thickness 180 mm (e.g. 3x60 mm)
8 Stone wool with one side stitched wire fencing
(min.density 105 kg/m³), thickness 60 mm
9 Duct
Used materials - example:*
3 Promapyr, Rockwool Steprock HD, Hilti CFS-CT B 1S 140/50
4 Promapyr. Rockwool Steprock HD. Hilti CFS-CT C 1S 140/50
5 Promastop - P, K, Hilti CFS-CT
6 Promatect - H
7 Rockwool Wired Mat 105 th. 3x60 mm
8 Rockwool Wired Mat 105 th. 60 mm
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws ≥3,5 mm
with corresponding length.
Distance between screws ≤200 mm.
* Stuffing box, fire protection mastic, cement lime
plate and insulation materials can be replaced by
another approved fire sealing system for damper
installation with equivalent material
properties.
** Depends on the distance of the flap from the
construction, when the maximum distance from
the construct is not limited and according to EN
15882-2 must use the required number of hinges
according to EN 13366-1:2014.
The duct at the point of penetration can be
anchored to the fire wall construction!
Shown schemes of incorporation and damper
are illustrative only!