AC POWER SUPPLY MODULE REPLACEMENT PROCEDURE  |  PART NO. 

24732 

REV 

B.0

4

MODEL ADH NEMA

AC POWER SUPPLY MODULE

REPLACEMENT PROCEDURE

Once the four nuts and lock washers securing the 

mounting bracket to the front cover have been removed, 

move the existing power module and mounting bracket 

away from other components for greater clearance.

Note  the  configuration  of  the  five  electrical  leads 

connected to the existing AC power supply module. 

Refer to Figure 3 and Table 1. These leads will connect to 

the corresponding terminals on the new module. Using a 

Philips screwdriver, carefully loosen the set screws 

securing the electrical leads to the existing supply 

module terminals, then carefully remove the leads from 

the existing module. Also at this time, remove the 

jumper cable from across terminals 3 and 5 on the top 

side of the terminals.

7.

8.

Remove the two screws and lock washers connecting the 

power supply module to the mounting bracket.

Refer to Figure 4.

Set aside the mounting bracket and attaching hardware 

for re-use.

Using the two screws and lock washers removed in step 

9, install the new power supply module to the mounting 

bracket and torque to 8 in/lb.

Prior to installing the new power supply module and 

mounting bracket, connect the electrical leads and 

jumper to the new supply module as they were 

connected to the original module. Refer back to Figure 3 

and Table 1 on the previous page. Secure each lead and 

the jumper across terminals 3 and 5 by placing each lead 

behind the mounting screw from underneath then 

tightening the mounting screw inside each terminal. 

Gently tug on each lead to make sure it is fastened 

securely.

Once the five electrical leads and jumper are installed to 

the new supply module and the module itself is 

connected to the mounting bracket, install the mounting 

bracket over the Pem® studs on the inside of the front 

cover as the original module had been. Using the nut 

driver, install the four nuts and lock washers removed in 

step 6 and torque to 10 in/lb.

Reinstall the front cover removed in step 4. If it was 

placed upside down on the lid of the unit during this 

procedure, carefully turn the cover back over and work it 

back into position, past the wires and other components 

in the enclosure. Reinstall the four corner screws 

securing the front cover to the chassis.

Reconnect the ground wire by inserting it behind the 

retaining screw from which it was removed, then tighten 

the ground wire retaining screw. Reconnect the green 

power connector by holding it in place then tightening 

the two captive screws removed in step 3. Reconnect 

both ends of the orange Ethernet cable removed in step 

3. It does not matter which end of the Ethernet cable 

goes into which receptacle.

With the ground wire, power connector and Ethernet 

cable reconnected, close the lid of the NEMA enclosure 

and secure the two latches opposite the hinges. Secure 

the lid in place by reinstalling the two captive screws in 

the two outer corners of the lid.

Restore machine power by plugging the unit back in.

9.

10.

11.

12.

13.

14.

15

16.

Figure 3. - AC POWER SUPPLY MODULE ELECTRICAL CONNECTIONS

Figure 4. - THE AC POWER SUPPLY MODULE MOUNTING BRACKET SECURING SCREWS.

Jumper connects across 

terminals 3 and 5.

Insert Philips screwdriver into each access hole to loosen 

set screws.

1

2

3