ETCR 6000 Скачать руководство пользователя страница 6

 

-5- 

 
3

Measurement 

1) Power on 

2) Switch AC/DC key to choose the kind of measurement. 

3) Adjust zero 

4) Release the toroid lever to open clamp mouth and clamp measured conductors. 

5) Read LCD display data. In case 

OL A

 symbol was displayed, it means that current of measured 

line  is  beyond  the  maximum  limit  of  this  leaker;  with  this  case,  please  choose  leaker  with  much 

higher range limit. 

 
 
 
 
 
 
 
 
   
 
 
 

Clamp  positive  wire  and  negative  wire  together  is  to  measure  leakage  current  of  DC 
circuit. (Note: 2 wires) 
Clamp live wire and null line together is to measure AC leakage current. (Note: 2 wires) 
Clamp earth wire is to measure grounding line leakage current. (Note: single wire) 

 

Clamp main wire is to measure the current. (Note: single wire) 

 

4. Hold, Storage, Access Reading and Deleting 

1

Pressing 

HOLD

 key for a short time in the course of measurement (less than 3 seconds), 

DH

 

symbol will display, the leaker will hold current measuring data and automatically stored in the 

memory with a code; press 

HOLD

 key again to release the hold state, and the leaker continues 

its measuring; in case stored data reached to 60 groups, press 

HOLD

 key again, the 

FULL

 

symbol will display, which means storage memory is full; press 

HOLD

 key to cancel   

FULL

 

flickering and return to measuring mode.   

2

Long  press 

HOLD

  key  to  enter  into  data  access  mode  and  display  Unit  1  storage  data 

automatically; and then press 

HOLD

 key again to turn the page of stored data; null will display 

when there is no data in stored in the memory, power off the meter to exit data access mode.   

3

After entering into data access mode, press 

HOLD

 key for more than 3 seconds will clean up all 

stored data; when the leaker displaying 

dEL

 symbol, it means that it  has finished clean up 

process, and then return to measuring state automatically.   

5. Data Upload 

Make good connection of computer and the tester with RS232 communication wire, switch on the 

tester and run monitoring software. If the connection is successful, then it can read the stored historical 

data, upload to company, preserve and print.   

 
 
 

Содержание 6000

Страница 1: ......

Страница 2: ...I Electrical Signs 3 Ⅲ Technical Specifications 3 Ⅳ Structure 4 Ⅴ LCD Display 4 Ⅵ Operating Method 4 1 Start up Shutdown 4 2 Calibration 4 4 Hold Storage Access Reading and Deleting 5 5 Data Upload 5 Ⅶ How to Change Battery 6 Ⅷ Accessories 6 ...

Страница 3: ...e it and seal it for safekeeping immediately and then send it for disposal of authorized agency u Users shall carry out operation based on danger signs on leaker and manual u Users shall carry out safety operation based on instructions listed in this manual e g and danger signs on this manual I Introduction ETCR6000 AC DC Clamp Leaker is specially designed for measurement of AC DC current by adopt...

Страница 4: ...ng Rate 2 times s Frequency AC 45Hz 400Hz Polarity Indication DC current auto identified and display Test Position Tested wire in the jaw center Range Shift Automatically Line Voltage AC600V RS232 Interface Data stored in the memory of the meter via RS232 upload to PC Com Configure Baud rate 9600 data bit 8 stop bit 1 Data Memory 99units FULL blinks when the memory is full Reading Hold DH indicati...

Страница 5: ...the leaker will shut down automatically after flickering for 30s it will shut down formally to reduce battery consumption In case you have pressed HOLD key when LCD was flickering the leaker will continue to work for 5 minutes If the tester power off automatically the gear should firstly be switched to OFF for power on next time 2 Calibration When measuring first choose AC or DC gear adjust ZERO k...

Страница 6: ...a and automatically stored in the memory with a code press HOLD key again to release the hold state and the leaker continues its measuring in case stored data reached to 60 groups press HOLD key again the FULL symbol will display which means storage memory is full press HOLD key to cancel FULL flickering and return to measuring mode 2 Long press HOLD key to enter into data access mode and display ...

Страница 7: ...t off the battery to storage 1 symbol means the battery is undercharge and need to be replaced 2 Shut down the leaker before opening the battery cover please confirm the leaker is in off position and then replace with qualified new battery special attention shall be paid to polarity of battery at last cover battery cover plate Ⅷ Accessories Clamp tester 1 pc RS232 Com cable 1 pc Software 1 disk Ba...

Страница 8: ...CR Electronic Technology Company Address F 3F No 4 Pengshang Zhifu Road Jiahe Baiyun District Guangzhou Guangdong China Post Code 510440 Tel 86 20 62199556 62199553 Fax 86 20 62199550 E mail info etcr cc Website www etcr cc ...

Отзывы: