Step 6:

Attach the sensor to the mounting plate by aligning the tabs 
on the sensor with the slots on the mounting plate, then twist 
clockwise until the two are secured into place.

Soft Ceiling Tile Installation

Step 1:

Pull the Belden 8471 (or equivalent) and 14 AWG (2.5mm

2

ground wire to the installation location.

Step 2:

If you are installing the sensor in series with other 
sensors or stations

 (continuing the data run), use the 

provided EchoConnect pigtail, ESD ground pigtail and 
connectors (not provided)

 

to make the terminations. 

If you 

are not continuing the data run

, proceed 

to Step 3.

a: Strip each wire to the appropriate length, depending on 

the wire nut or other termination used (wire nuts are not 
provided).

b: Twist the data - (typically black) EchoConnect wire, the 

black lead from the EchoConnect pigtail, and any 
continuing EchoConnect (typically black) wire together 
and secure with the wire nut.

c: Repeat the above steps for the data + (typically white) 

EchoConnect wire, and for the ESD ground wires.

Step 3:

Create a hole for wire pass-through in the ceiling tile by 
poking through the center hole or oblong hole of the 
mounting plate, then pull the wires through.

Poke the adapter through the ceiling tile, then bend 

it over for a secure fit. 

EchoConnect pigtail 

and connectors

(optional use)

Terminate

 wires here

Содержание Unison Echo E-OCC

Страница 1: ...off functionality based on other connected control stations When manual control stations are present the sensor will only perform vacancy actions Each sensor is available in white or black finish Len...

Страница 2: ...nstall the sensor within eight feet from an HVAC airflow duct vent Install the sensor where it cannot easily sense movement in areas outside of the intended space such as hallways glass partitions or...

Страница 3: ...box finished ceiling or soft ceiling tile Determine the installation method and follow the detailed instructions See Junction Box Installation on page 4 See Soft Ceiling Tile Installation on page 5 Se...

Страница 4: ...the mounting plate Step 4 Secure the mounting plate to the junction box using the screws provided both short and long screws are provided for convenience Step 5 Strip each wire 5 16 8mm and terminate...

Страница 5: ...ot provided to make the terminations If you are not continuing the data run proceed to Step 3 a Strip each wire to the appropriate length depending on the wire nut or other termination used wire nuts...

Страница 6: ...terminal b Terminate the black incoming wire to the data terminal c Terminate the green yellow ground wire to the labeled ground terminal Sensor Configuration The Echo Occupancy Vacancy Sensor partic...

Страница 7: ...ings are ignored Instead the settings made by the EchoAccess Mobile App for Vacancy Timeout Enable PIR LED and Occupancy actions are used DIP Switch 3 4 DIP switch 3 4 set the Vacancy Timeout to 5 15...

Страница 8: ...hes MODE button and LED and the Auxiliary button See Preset below and Vacancy Timeout on page 9 for local configuration instructions Preset The MODE button and LED found on the rear panel of the senso...

Страница 9: ...release the MODE button to save the current setting The Mode Sensor count LED turns off and the A button again blinks out the saved preset index Step 4 Attach the sensor to the mounting plate by align...

Страница 10: ...curs during the grace period Lens Masking Lens masks are provided in the packaging for your convenience used to block a section of the lens from detecting occupancy PIR Detection The PIR detection aut...

Страница 11: ...alk Test feature at the sensor A green LED will begin to flash indicating Walk Test is enabled and the vacancy no vacancy occupancy timer will be shortened to 10 seconds Step 3 Move throughout the spa...

Страница 12: ...ft 6 1m 20ft 6 1m 20ft 9 1m 30ft 9 1m 30ft 12 2m 40ft 12 2m 40ft 0 12 2m 40ft 9 1m 30ft 6 1m 20ft Small Room side view 0 0 1 5m 5ft 1 5m 5ft 3 0m 10ft 3 0m 10ft 4 6m 15ft 4 6m 15ft 6 1m 20ft 6 1m 20ft...

Отзывы: