Occupancy/Vacancy Sensors offer a Walk Test mode which shortens the 
vacancy timer to 10 seconds, allowing for simple and quick verification of the 
sensors coverage and range in the installed space.

Enable Walk Test Mode

Step 1:

Prepare the site for configuration.

a: Make certain the sensor and lighting loads are powered 

and connected for control by the Echo controller.

b: You will need direct access to the Occupancy/Vacancy 

Sensor in order to place it into Walk Test mode. 

Step 2:

Press the 

[Walk Test]

 button on the front of the sensor to 

enable the Walk Test feature at the sensor. A green LED will 
begin to flash, indicating Walk Test is enabled and the 
vacancy/no vacancy occupancy timer will be shortened to 10 
seconds.

Step 3:

Move throughout the space including corners and areas that 
may specifically be obscured from line of sight to the sensor. 
Each time the sensor detects movement, the lens will 
illuminate red.

Step 4:

Adjust the lens masking, if installed, blocking certain areas of 
the installed space from sensor detection. See 

“Lens Masking”

 

on page

10

.

Step 5:

Walk Test mode will automatically exit after five minutes from 
the time it was enabled. To manually exit the Walk Test mode, 
press either of the buttons on the sensor.

Auxiliary 

button

Walk Test

button

Walk-Test mode automatically exits and the 
sensor returns to normal operation after 5 
minutes and can be manually terminated early by 
pressing the 

[Walk Test] 

button.

Содержание Unison Echo E-OCC

Страница 1: ...off functionality based on other connected control stations When manual control stations are present the sensor will only perform vacancy actions Each sensor is available in white or black finish Len...

Страница 2: ...nstall the sensor within eight feet from an HVAC airflow duct vent Install the sensor where it cannot easily sense movement in areas outside of the intended space such as hallways glass partitions or...

Страница 3: ...box finished ceiling or soft ceiling tile Determine the installation method and follow the detailed instructions See Junction Box Installation on page 4 See Soft Ceiling Tile Installation on page 5 Se...

Страница 4: ...the mounting plate Step 4 Secure the mounting plate to the junction box using the screws provided both short and long screws are provided for convenience Step 5 Strip each wire 5 16 8mm and terminate...

Страница 5: ...ot provided to make the terminations If you are not continuing the data run proceed to Step 3 a Strip each wire to the appropriate length depending on the wire nut or other termination used wire nuts...

Страница 6: ...terminal b Terminate the black incoming wire to the data terminal c Terminate the green yellow ground wire to the labeled ground terminal Sensor Configuration The Echo Occupancy Vacancy Sensor partic...

Страница 7: ...ings are ignored Instead the settings made by the EchoAccess Mobile App for Vacancy Timeout Enable PIR LED and Occupancy actions are used DIP Switch 3 4 DIP switch 3 4 set the Vacancy Timeout to 5 15...

Страница 8: ...hes MODE button and LED and the Auxiliary button See Preset below and Vacancy Timeout on page 9 for local configuration instructions Preset The MODE button and LED found on the rear panel of the senso...

Страница 9: ...release the MODE button to save the current setting The Mode Sensor count LED turns off and the A button again blinks out the saved preset index Step 4 Attach the sensor to the mounting plate by align...

Страница 10: ...curs during the grace period Lens Masking Lens masks are provided in the packaging for your convenience used to block a section of the lens from detecting occupancy PIR Detection The PIR detection aut...

Страница 11: ...alk Test feature at the sensor A green LED will begin to flash indicating Walk Test is enabled and the vacancy no vacancy occupancy timer will be shortened to 10 seconds Step 3 Move throughout the spa...

Страница 12: ...ft 6 1m 20ft 6 1m 20ft 9 1m 30ft 9 1m 30ft 12 2m 40ft 12 2m 40ft 0 12 2m 40ft 9 1m 30ft 6 1m 20ft Small Room side view 0 0 1 5m 5ft 1 5m 5ft 3 0m 10ft 3 0m 10ft 4 6m 15ft 4 6m 15ft 6 1m 20ft 6 1m 20ft...

Отзывы: