ETC Installation Guide

Occupancy/Vacancy Sensor

Echo Occupancy/Vacancy Sensor

 Page 2 of 12

Electronic Theatre Controls, Inc.

Wire Specification

Sensors connect to the EchoConnect communication bus. EchoConnect is a 
bidirectional protocol that uses one pair of wires (data + and data -) for both 
data and power. ETC recommends using Belden 8471 (or approved equal) 
Class II wire. The total combined length of an EchoConnect wire run (using 
Belden 8471, or equal) may not exceed 1,640 feet (500m).

Installation Environment

Occupancy/Vacancy Sensors are intended for installation to a finished ceiling 
surface, ceiling tile mounted, attached to a round fixture junction box or 
single-gang RACO switch box. 

The sensor operates in ambient temperatures of 0°C to 40°C, with a maximum 
of 90% non-condensing humidity.

ETC recommends paying special attention to the installation environment:

• The sensor must have an unobstructed view of the room. Do not mount 

behind or near tall cabinets, shelves, hanging light fixtures, etc.

• Do not install the sensor within eight feet from an HVAC airflow duct/

vent.

• Install the sensor where it cannot easily sense movement in areas 

outside of the intended space, such as hallways, glass partitions, or 
adjacent rooms. If the installation location cannot avoid these 

Note:

All control wiring should be installed and terminated by a qualified 
installer and should follow standard wiring installation practices.

Leave approximately 10 inches (254mm) of wiring in the back box for 
connection to allow slack for future service needs.

Note:

ETC requires that all sensors be grounded. Pull an additional 14 AWG 
(1.5mm

2

) wire for grounding when control wires are not installed in 

grounded metal conduit.

Note:

- When using Category5 (or equivalent) cable on the EchoConnect 
communication bus, please note the following:
- Cat5 wiring must be terminated using EchoConnect Cat5 
Termination Kit and must be installed using a bus topology. Refer to 
the installation guide that is provided with the Cat5 Termination Kit 
(7186A1207) for information to terminate Cat5 wiring.
- Not all topologies are supported using Cat5; careful planning is 
required to ensure the proper termination kits are available and the 
wire is pulled appropriately.

Содержание Unison Echo E-OCC

Страница 1: ...off functionality based on other connected control stations When manual control stations are present the sensor will only perform vacancy actions Each sensor is available in white or black finish Len...

Страница 2: ...nstall the sensor within eight feet from an HVAC airflow duct vent Install the sensor where it cannot easily sense movement in areas outside of the intended space such as hallways glass partitions or...

Страница 3: ...box finished ceiling or soft ceiling tile Determine the installation method and follow the detailed instructions See Junction Box Installation on page 4 See Soft Ceiling Tile Installation on page 5 Se...

Страница 4: ...the mounting plate Step 4 Secure the mounting plate to the junction box using the screws provided both short and long screws are provided for convenience Step 5 Strip each wire 5 16 8mm and terminate...

Страница 5: ...ot provided to make the terminations If you are not continuing the data run proceed to Step 3 a Strip each wire to the appropriate length depending on the wire nut or other termination used wire nuts...

Страница 6: ...terminal b Terminate the black incoming wire to the data terminal c Terminate the green yellow ground wire to the labeled ground terminal Sensor Configuration The Echo Occupancy Vacancy Sensor partic...

Страница 7: ...ings are ignored Instead the settings made by the EchoAccess Mobile App for Vacancy Timeout Enable PIR LED and Occupancy actions are used DIP Switch 3 4 DIP switch 3 4 set the Vacancy Timeout to 5 15...

Страница 8: ...hes MODE button and LED and the Auxiliary button See Preset below and Vacancy Timeout on page 9 for local configuration instructions Preset The MODE button and LED found on the rear panel of the senso...

Страница 9: ...release the MODE button to save the current setting The Mode Sensor count LED turns off and the A button again blinks out the saved preset index Step 4 Attach the sensor to the mounting plate by align...

Страница 10: ...curs during the grace period Lens Masking Lens masks are provided in the packaging for your convenience used to block a section of the lens from detecting occupancy PIR Detection The PIR detection aut...

Страница 11: ...alk Test feature at the sensor A green LED will begin to flash indicating Walk Test is enabled and the vacancy no vacancy occupancy timer will be shortened to 10 seconds Step 3 Move throughout the spa...

Страница 12: ...ft 6 1m 20ft 6 1m 20ft 9 1m 30ft 9 1m 30ft 12 2m 40ft 12 2m 40ft 0 12 2m 40ft 9 1m 30ft 6 1m 20ft Small Room side view 0 0 1 5m 5ft 1 5m 5ft 3 0m 10ft 3 0m 10ft 4 6m 15ft 4 6m 15ft 6 1m 20ft 6 1m 20ft...

Отзывы: